Control of three-phase grid connected converter based on harmonic power injection method under the non-ideal grid voltage conditions

被引:0
|
作者
Zhou X. [1 ]
Chen H. [1 ]
Xu H. [1 ]
机构
[1] Department of Electrical Engineering, Harbin Institute of Technology, Harbin, 150001, Heilongjiang Province
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2016年 / 36卷 / 01期
关键词
Direct power control; Extended state observer; Harmonic reduction; Power system harmonics; PWM power converters; Three-phase grid connected converter;
D O I
10.13334/j.0258-8013.pcsee.2016.01.023
中图分类号
学科分类号
摘要
Under the non-ideal grid voltage conditions, which are distorted or unbalanced grid voltages, the conventional control strategy for three-phase grid connected converter would not be able to obtain satisfactory results. Therefore, based on the relationship between the power flows under non-ideal voltage conditions and the ideal "average unit power factor with sinusoidal currents", the power flow equations for the three control targets are deduced respectively in this paper. This paper achieves three control targets by harmonic power injection method respectively. Finally, a linear active disturbance rejection control (LADRC) is designed to improve the system's performance. Experiments show that the proposed methods have the advantages of simple structure, low harmonics etc. © 2016 Chin. Soc. for Elec. Eng.
引用
收藏
页码:215 / 223
页数:8
相关论文
共 28 条
  • [1] Rodriguez J.R., Dixon L.W., Espinoza J.R., Et al., PWM regenerative rectifiers: state of the art, IEEE Transactions on Industrial Electronics, 52, 1, pp. 5-22, (2005)
  • [2] Deng W., Zhang B., Qiu D., Et al., The research of decoupled state variable feedback linearization control method of three-phase voltage source PWM rectifier, Proceedings of the CSEE, 25, 7, pp. 97-103, (2005)
  • [3] Vazquez S., Sanchez J.A., Carrasco J.M., Et al., A model-based direct power control for three-phase power converters, IEEE Transactions on Industrial Electronics, 55, 4, pp. 1647-1657, (2008)
  • [4] Song Z.F., Xia C.L., Liu T., Predictive current control of three-phase grid-connected converters with constant switching frequency for wind energy systems, IEEE Transactions on Industrial Electronics, 60, 6, pp. 2451-2464, (2013)
  • [5] Chen Y., Luo A., Zhou L., Et al., A robust predictive deadbeat grid-connected control method based on power feed-forward control, Proceedings of the CSEE, 33, 36, pp. 62-70, (2013)
  • [6] Wang J., Yang X., Control strategy of voltage source PWM rectifiers under unbalanced voltage conditions, Proceedings of the CSEE, 31, 18, pp. 14-20, (2011)
  • [7] Zhao R., He Y., Virtual line-flux-linkage oriented vector control of three-phase voltage source PWM rectifier without line voltage sensors, Proceedings of the CSEE, 25, 20, pp. 56-61, (2005)
  • [8] Antoniewicz P., Kazmierkowski M.P., Virtual-flux-based predictive direct power control of AC/DC converters with online inductance estimation, IEEE Transactions on Industrial Electronics, 55, 12, pp. 4381-4390, (2008)
  • [9] Zhou H., Wen X., Zhao F., Et al., A novel adaptive dead-time compensation strategy for VSI, Proceedings of the CSEE, 31, 24, pp. 26-32, (2011)
  • [10] Hu Q., Lu Z., A novel method for dead-time compensation based on SVPWM, Proceedings of the CSEE, 25, 3, pp. 15-19, (2005)