Damage and failure study of Sichuan electric power grid in Wenchuan earthquake

被引:0
作者
Liu R. [1 ]
Zhang M. [1 ]
Wu Y. [1 ]
Liu Y. [2 ]
Lin J. [1 ]
Guo E. [1 ]
机构
[1] Institute of Engineering Mechanics, China Earthquake Administration
[2] State Grid Power Company in Sichuan Province
来源
Yingyong Jichu yu Gongcheng Kexue Xuebao/Journal of Basic Science and Engineering | 2010年 / 18卷 / SUPPL. 1期
关键词
Earthquake damage; Electric power system; Function failure; High voltage electric equipment; Wenchuan Earthquake;
D O I
10.3969/j.issn.1005-0930.2010.s1.023
中图分类号
学科分类号
摘要
The overall damage and losses of Sichuan electric power system caused by Wenchuan earthquake were introduced. The damage situation of substations at 110 kV and above were listed, which were located in areas with earthquake intensity IX and above and managed by the state grid company in Sichuan Province. The major damage phenomena of indoor and outdoor high-voltage electrical equipments, transmission towers, distribution poles and lines were summarized. The statistics of the damage frequency, interruption situation and recovery time of substations at different levels of intensity were given. On these grounds, the Wenchuan quake damage characteristics of electric facilities in areas with intensity VI to XI, and the failure mode of electric systems were summarized. The main factors for this quake damage to the systems were analyzed. Several new measures and suggestions to strengthen the system's weakness had been put forward. The results can provide the reference for rapid evaluating the substations damage and improving the electric facilities seismic reliability.
引用
收藏
页码:200 / 211
页数:11
相关论文
共 9 条
[1]  
Wenchuan earthquake disaster assessment report, (2008)
[2]  
Wenchuan Earthquake Sichuan power grid electrical equipment damage report, pp. 1-2, (2008)
[3]  
Equipments and facilities damage introduce of Sichuan power grid in 5.12 Wenchuan Earthquake, pp. 5-8, (2008)
[4]  
Guideline for assessing the performance of electric power systems in natural hazard and human threat events: Report of ALA Scientific Group, (2005)
[5]  
Anagnos T., Development of an electrical substation equipment performance database for evaluation of equipment fragilities, (1999)
[6]  
Dobson I., Where is the edge for cascading failure? Challenges and opportunities for quantifying blackout risk, IEEE Power Engineering Society General Meeting, (2007)
[7]  
Nedic D.P., Dobson I., Kirschen D.S., Et al., Criticality in a cascading failure blackout model, International Journal of Electrical Power and Energy System, 28, pp. 627-633, (2006)
[8]  
Liu H., Seismic Disasters of Tangshan Earthquake II, pp. 742-748, (1986)
[9]  
Yin R., Li D., Liu G., Et al., High-voltage transmission towers earthquake damage and seismic study, World Earthquake Engineering, 21, 1, pp. 51-54, (2005)