A fast faulty phase selection method based on S-transform

被引:0
作者
Liu, Dong [1 ]
Zou, Guibin [1 ]
Wang, Xin [2 ]
Gao, Houlei [1 ]
Ma, Yueyang [1 ]
机构
[1] Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education, Shandong University, Jinan, 250061, Shandong Province
[2] State Grid Shandong Electric Power Research Institute, Jinan, 250002, Shandong Province
来源
Dianwang Jishu/Power System Technology | 2015年 / 39卷 / 12期
基金
中国国家自然科学基金;
关键词
Fault component; Faulty phase selection; Model phasor; S-transform; Waveform integration;
D O I
10.13335/j.1000-3673.pst.2015.12.040
中图分类号
学科分类号
摘要
Traditional phase selection method can't keep up with development of extra high speed transient protection. This paper proposes a novel approach for faulty phase selection based on S-transform and phase current integration. This approach stems from analyzing modular characteristics of various types of faults and characteristics of phase currents for two phase grounding fault. Phase selection algorithm uses S-transform to obtain single frequency phasor of module components at a specific time, and relations among module phasorsare analyzed to classify fault types. The algorithm uses phase current integration to distinguish faulty phases in two phase grounding circumstance. PSCAD simulation results show that the algorithm can quickly and accurately find out fault phases, not affected by fault position, fault inception angle, fault resistance and structure of buses. © 2015, Power System Technology Press. All right reserved.
引用
收藏
页码:3603 / 3608
页数:5
相关论文
共 18 条
  • [1] Chamia M., Liberman S., Ultra high speed relay for EHV/UHV transmission lines-development, design and application, IEEE Transactions on Power Apparatus and Systems, 6, pp. 2104-2116, (1978)
  • [2] Dong X., Ge Y., Dong X., Et al., Wavelet transform based distance protection scheme with travelling wave fault location, Power System Technology, 25, 7, pp. 9-13, (2001)
  • [3] Duan J., Zhang B., Study of starting algorithm using travelling-waves, Proceedings of the CSEE, 24, 9, pp. 30-36, (2004)
  • [4] Ha H., Zhang B., Lu Z., A novel principle of non-unit protection based on transient components for EHV transmission lines, Proceedings of the CSEE, 20, 11, pp. 56-61, (2000)
  • [5] Lin X., Liu P., Yang C., Et al., A wavelet analysis based non-communication protection scheme for transmission lines, Proceedings of the CSEE, 21, 6, pp. 9-14, (2001)
  • [6] Duan J., Zhang B., Zhou Y., Study of ultra-high-speed transient-based directional relay, Proceedings of the CSEE, 25, 4, pp. 7-12, (2005)
  • [7] Huang S.F., Luo L., Cao K., A novel method of ground fault phase selection in weak-infeed side, IEEE Transactions on Power Delivery, 29, 5, pp. 2215-2222, (2014)
  • [8] Lin S., Mei J., Chen S., Et al., Fault detection and faulty phase determination of transmission lines based on time-frequency characteristics of transient travelling waves, Power System Technology, 36, 7, pp. 48-53, (2012)
  • [9] Duan J., Zhang B., Zhou Y., Et al., Transient-based faulty phase selection in EHV transmission lines, Proceedings of the CSEE, 26, 3, pp. 1-6, (2006)
  • [10] Yang Y., Yu W., Tai N., A one terminal transient energy based faulty phase selection method for protection of double circuit lines, Power System Technology, 29, 13, pp. 65-68, (2005)