Optimized capacity configuration of photovoltaic generation and energy storage device for stand-alone photovoltaic generation system

被引:0
作者
机构
[1] School of Electric and Electronic Engineering, North China Electric Power University, Beijing 102206, Changping District
[2] China Electric Power Research Institute, Beijing 100192, Haidian District
[3] Sungrow Power Supply Co., Ltd., Hefei 230088, Anhui Province
来源
Wu, X. (wuxg1014@163.com) | 1600年 / Power System Technology Press卷 / 38期
关键词
Capacity configuration; Energy excess percentage; Energy storage; Loss of power supply probability; Stand-alone PV system;
D O I
10.13335/j.1000-3673.pst.2014.05.022
中图分类号
学科分类号
摘要
To enhance power supply reliability of stand-alone photovoltaic (PV) generation system and improve PV utilization, it is necessary to configure the capacity of PV modules and energy storage devices reasonably. Based on the feature of joint-operation of PV generation system with energy storage device and considering dynamic variation of stored energy during the joint operation, taking technical characteristics of energy storage unit as the constraint a joint configuration method of PV capacity and energy storage capacity, in which the loss of power supply probability (LPSP) and energy excess percentage (EXC) are taken as assessment indices, is proposed. Under the conditions of a given case, taking three kinds of batteries, namely the valve regulated lead acid battery (VRLAB), the lithium-ion battery and all-vanadium redox flow battery, into account, the capacity of the three kinds of batteries are respectively configured and taking the minimized initial investment as the objective, the optimized capacity configuration of PV modules and energy storage units is computed. Computation results show that under the same configuration a higher power supply reliability can be achieved by use of all-vanadium redox flow battery, however under the condition of satisfying the requirement of indices, the initial investment can be the minimum while the VRLAB is adopted.
引用
收藏
页码:1271 / 1276
页数:5
相关论文
共 20 条
  • [1] Xiao H., Liu S., Zheng L., Et al., A preliminary research on microgrid technology, Power System Protection and Control, 37, 8, pp. 114-119, (2009)
  • [2] Xxu L., Ruan X., Zhang B., Et al., An improved optimal sizing method for wind-solar-battery hybrid power system, Proceedings of the CSEE, 32, 25, pp. 88-98, (2012)
  • [3] Kang L., Guo H., Wu J., Et al., Characteristics of distributed generation system and related research issues caused by connecting it to power system, Power System Technology, 34, 11, pp. 43-47, (2010)
  • [4] Zhang G., Tang X., Qi Z., Application of hybrid energy storage system of super-capacitors and batteries in a microgrid, Automation of Electric Power Systems, 34, 12, pp. 85-89, (2010)
  • [5] Luo C., Ooi B.-T., Frequency deviation of thermal power plants due to wind farms, IEEE Trans on Energy Conversion, 21, 3, pp. 708-716, (2006)
  • [6] Zhang K., Mao C., Xie J., Et al., Optimal design of hybrid energy storage system capacity for wind farms, Proceedings of the CSEE, 32, 25, pp. 79-87, (2012)
  • [7] Shiji W., Ryohei O., An Investigation on Optimal Battery Capacity in Wind Power Generation System, (2004)
  • [8] Liang L., Li J., Hui D., Optimization configuration for capacity of energy storage system in large-scale wind farm, High Voltage Engineering, 37, 4, pp. 930-936, (2011)
  • [9] Li Q., Choi S.S., Yuan Y., On the determination of battery energy storage capacity and short-term power dispatch of a wind farm, IEEE Trans on Sustainable Energy, 2, 2, pp. 148-158, (2011)
  • [10] Xie S., Yang L., Li L., A chance constrained programming based optimal configuration method of hybrid energy storage system, Power System Technology, 36, 5, pp. 79-84, (2012)