Analysis on secondary single-phase grounding short circuit fault of voltage transformer

被引:0
|
作者
Qin, Tao [1 ]
Zhang, Lei [1 ]
Wang, Xiang-Dong [1 ]
机构
[1] Yinnan Power Supply Bureau, Wuzhong 751100, China
关键词
Analysis - Grounding current - Potential transformer - Preventive measures - Secondary voltage - Short-circuit fault - Single phase grounding - Voltage transformer;
D O I
暂无
中图分类号
学科分类号
摘要
When single-phase of potential transformer secondary winding grounds, it raises the voltage of the other two non-fault phases. By measuring the impedance of secondary voltage cable and changing the grounding points, this paper analyzes and expatiates the reason is that the N-phase current of secondary electric cable generates voltage to the other two non-fault phases when grounding current affluxes it. The ways of preventing its effection to electric network are extending the section of N-phase electric cable or blocking the overvoltage protection.
引用
收藏
页码:136 / 138
相关论文
共 50 条
  • [1] Analysis of the influence of single-phase grounding fault on the power characteristics of grounding transformer
    Xian R.-C.
    Chen L.
    Zheng C.-X.
    Zhang B.-Q.
    Gao H.-P.
    Fan H.-F.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2022, 26 (06): : 134 - 141
  • [2] Adaptability analysis of photovoltaic power station main transformer ratio differential protection to single-phase grounding short circuit fault
    Chen X.
    Zhu Y.
    Zhang H.
    Wang C.
    Xue Z.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2023, 43 (10): : 217 - 224
  • [3] Analysis of the operational characteristics of a grounding transformer when there is a single-phase grounding fault of the system
    Chen, Lei
    Xian, Richang
    Zheng, Chunxu
    Gao, Hongpeng
    Fan, Huifang
    Zhang, Bingqian
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (12): : 56 - 64
  • [4] Influence of System Single-phase Grounding Fault on Load Loss of Grounding Transformer
    Chen L.
    Xian R.
    Li F.
    Xie T.
    Zhang B.
    Zhao Y.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (11): : 3941 - 3948
  • [5] Effects of Neutral Point Grounding Methods on Single-Phase Short Circuit Fault Characteristics
    Kokor, Amela
    Smaka, Senad
    Grebovic, Selma
    Helac, Vahid
    2022 21ST INTERNATIONAL SYMPOSIUM INFOTEH-JAHORINA (INFOTEH), 2022,
  • [6] Online identification of single-phase grounding fault at low-voltage side of excitation transformer
    Chen, Jun, 1600, Electric Power Automation Equipment Press (34):
  • [7] A novel single-phase grounding fault voltage full compensation topology based on antiphase transformer
    Cai, Xiaobin
    Liu, Hongwen
    Huang, Xiaohui
    Huang, Chunhui
    Chai, Chenchao
    Rong, Fei
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2021, 15 (20) : 2893 - 2904
  • [8] Analysis of Voltage Characteristics for Single-Phase Line Break Fault in Resonant Grounding Systems
    Li, He
    Xue, Yongduan
    Chen, Mengqi
    Zhang, Zhongxia
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (02) : 1416 - 1425
  • [9] Phase Offset Characteristics of Commutation Voltage for HVDC with Single-phase Grounding Fault
    Huang M.
    Fu C.
    Wang J.
    Yang J.
    Li H.
    Wen Z.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (12): : 162 - 168
  • [10] Research on a single-phase grounding fault handling true test of primary and secondary integration circuit breaker
    Li H.
    Tian Y.
    Chen J.
    Shao M.
    Wan B.
    Dai M.
    Wu X.
    Cheng T.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (12): : 158 - 165