Design of multi-channel additional robust controller for HVDC transmission system

被引:0
作者
Li, Baohong [1 ]
Zhang, Yingmin [1 ]
Li, Xingyuan [1 ]
Liu, Tianqi [1 ]
Zhao, Rui [1 ]
机构
[1] School of Electrical Engineering and Information, Sichuan University, Chengdu 610065, Sichuan Province
来源
Dianwang Jishu/Power System Technology | 2014年 / 38卷 / 04期
关键词
Additional control for HVDC power transmission; Linear matrix inequality; Multi-channel; Robust control;
D O I
10.13335/j.1000-3673.pst.2014.04.006
中图分类号
学科分类号
摘要
The reduced order model of the system and related oscillation frequency are identified by total least squares-estimation on signal parameters via rotational technique (TLS-ESPRIT) algorithm, and then using the linear matrix inequality (LMI) based robust control design method a multi-channel additional controller for different oscillation modes occurred in HVDC power transmission system is designed. The balanced truncation method is used to reduce the order of the controller, and both performance optimization and robustness of the controller are taken into account, meanwhile low-frequency oscillation and sub-synchronous oscillation can be suppressed simultaneously. The interaction between control channels is restrained by Butterworth filter in each control channel. To validate the performance of the designed controller, a traditional PID controller is design as the contrast. Simulation results show that the designed multi-channel robust controller can well suppress different oscillation modes simultaneously and possesses strong robustness. Besides, to be convenient for practical application, output feedback control is utilized in the design of the controller.
引用
收藏
页码:858 / 864
页数:6
相关论文
共 23 条
  • [11] Jiang P., Ye H., Wu X., Residue-based robust control method for additional damping controller of static synchronous compensator, Power System Technology, 36, 10, pp. 131-135, (2012)
  • [12] Ogata K., Modern Control Engineering, pp. 612-620, (2010)
  • [13] pp. 117-121, (2008)
  • [14] pp. 104-107, (2002)
  • [15] Scherer C., Gahinet P., Chilali M., Multiobjective output-feedback control via LMI optimization, IEEE Transactions on Automatic Control, 42, 7, pp. 896-911, (1997)
  • [16] Pal B.C., Coonick A.H., Jaimoukha I.M., Et al., A linear matrix inequality approach to robust damping control design in power systems with superconducting magnetic energy storage device, IEEE Transactions on Power Systems, 15, 1, pp. 356-362, (2000)
  • [17] Pal B.C., Robust damping of interarea oscillations with unified power-flow controller, IEE Proceedings-Generation Transmission and Distribution, IET, 149, 6, pp. 733-738, (2002)
  • [18] Tripathy P., Srivastava S.C., Singh S.N., A modified TLS-ESPRIT-based method for low-frequency mode identification in power systems utilizing synchrophasor measurements, IEEE Transactions on Power Systems, 26, 2, pp. 719-727, (2011)
  • [19] Wang X., Li X., Wang Y., Et al., Analysis on controllability sensitive points of multi-HVDC systems based on TLS-ESPRIT method, Power System Protection and Control, 40, 19, pp. 121-125, (2012)
  • [20] Zhang Y., Bose A., Design of wide-area damping controllers for interarea oscillations, IEEE Transactions on Power Systems, 23, 3, pp. 1136-1143, (2008)