A hybrid load prediction method of office buildings based on physical simulation database and LightGBM algorithm

被引:10
作者
Lian, Huihui [1 ,2 ]
Ji, Ying [1 ,2 ]
Niu, Menghan [1 ,2 ]
Gu, Jiefan [3 ]
Xie, Jingchao [1 ,2 ]
Liu, Jiaping [1 ,2 ]
机构
[1] Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China
[2] Beijing Univ Technol, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
[3] Tongji Univ, Coll Architecture & Urban Planning, Shanghai 201804, Peoples R China
关键词
Office building; Load prediction; Simulation database; LightGBM; Feature engineering; ENERGY-CONSUMPTION; ARTIFICIAL-INTELLIGENCE; NEURAL-NETWORK; LEVEL; CAPABILITIES;
D O I
10.1016/j.apenergy.2024.124620
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Building load prediction plays an important role in building energy savings and mechanical and electrical system optimization control. The dynamic energy consumption can be accurately calculated using the traditional physical energy simulation method that entails a complex setup and verification process due to the numerous input parameters required. It is also difficult to change the physical model once it has been determined. The datamining method is fast in calculation and simple to use, but its prediction accuracy is limited by historical data quality. It is difficult to predict the load of new buildings without historical data. To solve these problems, this study proposes a hybrid building load prediction method for office buildings. The proposed method uses EnergyPlus to generate a building load database that includes than 25.14 million data cases, covering 35 types of building geometry and 2870 building examples. Based on the above database, the LightGBM algorithm was selected to extract feature variables that affect the load and build a load prediction model. The training results show that there are 24 key feature variables for office building load prediction. The hourly MAPE of the cooling load prediction model is 6.95 % and RMSE is 4.31 W/m2, and the hourly MAPE of the heating load prediction model is 7.09 % and RMSE is 11.64 W/m2 compared with EnergyPlus model. Two actual office buildings are selected as case studies to validate the model prediction accuracy. Results show that comparing predicted results with measured data, the hourly cooling load of the MAPE is 12.42 %. Coparing predicted results with actual heating load, daily MAPE is 7.97 %.
引用
收藏
页数:15
相关论文
共 67 条
[1]  
[Anonymous], 2015, Remarks by President Xi jinping at the Opening ceremony of the Paris Climate Change Conference
[2]   Integrated energy and environmental life cycle assessment of office building envelopes [J].
Azari, Rahman .
ENERGY AND BUILDINGS, 2014, 82 :156-162
[3]   Day-ahead building-level load forecasts using deep learning vs. traditional time-series techniques [J].
Cai, Mengmeng ;
Pipattanasomporn, Manisa ;
Rahman, Saifur .
APPLIED ENERGY, 2019, 236 :1078-1088
[4]  
Chen FY, 2013, Building Science, V29, P103
[5]  
China Academy of Building Research, 2013, Standard for lighting Design of Buildings:GB 50034-2013
[6]  
Chu YN, 2019, Building Science, V35, P8
[7]   Contrasting the capabilities of building energy performance simulation programs [J].
Crawley, Drury B. ;
Hand, Jon W. ;
Kurnmert, Michal ;
Griffith, Brent T. .
BUILDING AND ENVIRONMENT, 2008, 43 (04) :661-673
[8]  
[丁研 Ding Yan], 2019, [土木与环境工程学报(中英文), Journal of Civil and Environmental Engineering], V41, P174
[9]   Predicting future hourly residential electrical consumption: A machine learning case study [J].
Edwards, Richard E. ;
New, Joshua ;
Parker, Lynne E. .
ENERGY AND BUILDINGS, 2012, 49 :591-603
[10]  
Feng JT, 2012, Building Energy Efficiency, V40, P64