Study on limits of power frequency electric field on house platform near AC transmission lines

被引:0
作者
China Electric Power Research Institute, Haidian District,, Beijing [1 ]
100192, China
不详 [2 ]
100031, China
不详 [3 ]
100052, China
机构
[1] China Electric Power Research Institute, Haidian District,, Beijing
[2] State Grid corporation of China, Xicheng District,, Beijing
[3] AC Engineering Construction Company of State Grid Corporation of China, Xicheng District,, Beijing
来源
Dianwang Jishu | / 6卷 / 1532-1537期
关键词
AC transmission lines; House balcony; House platform; Human body perception test; Limits of power frequency electric field;
D O I
10.13335/j.1000-3673.pst.2015.06.010
中图分类号
学科分类号
摘要
During the evaluation of electromagnetic environment for high voltage power transmission projects nearby houses, the measurement of power frequency electric field on the house platform and be limited to 4 kV/m was often required. For this situation that the methods of measurement exist but no reference limit value, the experiments of human body direct feeling and transient shocks feeling which including insulated person touching the grounded metal and grounded person touching the insulated metal under different power frequency electric field values were conducted. Considering the direct feeling and possible transient shocks of human body under power frequency electric field, the limit of 7 kV/m at 1.5 m high from the bottom of the house platform where the residents didn't appear frequently was proposed. And the limit of 4 kV/m at 1.5 m high from the bottom of the house platform (include house balcony) where the residents appear frequently was also proposed, which is the same with the limit at the ground of first floor. ©, 2015, Power System Technology Press. All right reserved.
引用
收藏
页码:1532 / 1537
页数:5
相关论文
empty
未找到相关数据