Experimental study on coordination of protection for low-voltage AC network in DC zonal distribution system

被引:0
|
作者
机构
[1] National Key Laboratory for Vessel Integrated Power System Technology, Naval University of Engineering, Wuhan 430033, Hubei Province
来源
Wang, R. (wangrt4321@163.com) | 1600年 / Power System Technology Press卷 / 38期
关键词
AC micro grid; Experiment; Power electronics; Protection;
D O I
10.13335/j.1000-3673.pst.2014.05.021
中图分类号
学科分类号
摘要
In the conventional AC low-voltage network of the shipboard power system, the overcurrent protection is implemented by the overcurrent protective devices and the time-current curves. The AC low-voltage grid gets power from the inverters in the DC zonal electrical distribution system (DC-ZEDS), which is a newstyle shipboard distribution system. The overcurrent output capability of inverters is limited, but the nearest utility protective devices need enough short-circuit current to clear the short-circuit fault immediately, therefore it is a problem to coordinate the inverters with the downstream protective devices in the shipboard AC low-voltage grid. The protection method for shipboard AC low-voltage grid in DC-ZEDS is discussed through three aspects, namely the main circuit topology of the inverter module, its control strategy, the setting and configuration of protective devices like circuit breakers and fuses. A simulation platform is built based on the PSCAD environment, in which an AC low-voltage network supplied by inverters is constructed, and related experiments are performed. Results from both simulation and experiments show that the proposed protection method is rational.
引用
收藏
页码:1264 / 1270
页数:6
相关论文
共 21 条
  • [1] Ma W., Development of vessel integrated power system, Proceeding of International Conference on Electrical Machines and Systems (ICEMS), pp. 1-12, (2011)
  • [2] Doerry N.H., Fireman H., Designing all electric ships, Proceedings of the Ninth International Marine Design Conference, pp. 475-797, (2006)
  • [3] Fang M., Fu L., Wang R., Et al., Coordination protection for DC distribution network in DC zonal shipboard power system, Proceedings of International Conference on Advanced Power System Automation and Protection (APAP), pp. 418-421, (2011)
  • [4] Baran M.E., Mahajan N.R., Overcurrent protection on voltage-source-converter-based multiterminal DC distribution systems, IEEE Trans on Power Delivery, 22, 1, pp. 406-412, (2007)
  • [5] Tang L.X., Ooi B.T., Locating and Isolating DC Faults in Multi-Terminal DC Systems, IEEE Trans on Power Delivery, 22, 3, pp. 1877-1884, (2007)
  • [6] Zgliczynski J.B., Heiberger M., Callis S.I., Development of integrated fight-through power modules for the U.S. Navy fleet, Proceedings of AES, pp. 275-283, (2003)
  • [7] (2004)
  • [8] (2010)
  • [9] Wang X., Zhang C., Design and implementation of grid-connected seamless transfer algorithm for distributed generation systems, Power System Technology, 36, 7, pp. 191-194, (2012)
  • [10] Li S., Li Y., Sun J., Et al., A power quality control algorithm for micro-grid based on control strategy of inverter interfaced distributed generator, Power System Technology, 34, 8, pp. 6-11, (2010)