In order to improve the accuracy and reliability of single-phase grounding fault feeder selection in distribution network, a fault line selection method based on traveling wave panoramic waveform in time-frequency domain is proposed. First, the S-transform is used to extract the time-frequency traveling wave panoramic waveform of each line, which can display truly the characteristics of the fault traveling. The difference of amplitude, frequency and polarity of traveling wave between faulty line and healthy line is analyzed in detail. Then, based on the principle of waveform similarity, the traveling wave panoramic waveform of faulty line and healthy lines are analyzed quantitatively, and a similarity degree coefficient matrix is constructed for each line. By calculating the sum of the correlation coefficients of each line, the difference of the panoramic waveform is amplified, and the accurate distribution network line selection is realized. The proposed faulty line selection method does not need to set the threshold manually. A large number of simulation results show that the method has high algorithm adaptability. Under 3kΩ high-resistance ground fault, it can still achieve sensitively faulty feeder selection in distribution network. © 2021, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:2861 / 2870
页数:9
相关论文
共 22 条
  • [1] Guo Fengyi, Gao Hongxin, Tang Aixia, Et al., Series arc fault detection and line selection based on local binary pattern histogram matching, Transactions of China Electrotechnical Society, 35, 8, pp. 1653-1661, (2020)
  • [2] Deng Feng, Li Peng, Zeng Xiangjun, Et al., Fault line selection and location method based on synchrophasor measurement unit for distribution network, Automation of Electric Power Systems, 44, 19, pp. 160-171, (2020)
  • [3] Wang Yuanyuan, Huang Yuhao, Zeng Xiangjun, Faulty feeder detection of single phase-earth fault using grey relation degree in resonant grounding system, IEEE Transactions on Power Delivery, 32, 1, pp. 55-61, (2017)
  • [4] Liang Rui, Wang Chonglin, Fault line selection for single-phase-to-earth faults based on zero sequence transient current and grey relation analysis, Journal of Central South University, 41, 2, pp. 585-591, (2010)
  • [5] Long Yi, Ouyang Jinxin, Xiong Xiaofu, Et al., Protection principle of single-phase high resistance fault for distribution network base on zero-sequence power variation, Transactions of China Electrote-chnical Society, 34, 17, pp. 3687-3695, (2019)
  • [6] Tang Tao, Huang Chun, Jiang Yaqun, Et al., A method of fault line selection in resonant earthed system based on zero sequence impedance characteristic of lines, Transactions of China Electrotechnical Society, 31, 20, pp. 192-201, (2016)
  • [7] Shu Hongchun, Gong Zhen, TianXincui, Et al., Single line-to-ground fault line selection based on fault characteristic frequency band and morphological spectrum, Power System Technology, 43, 3, pp. 1041-1053, (2019)
  • [8] Liu Mouhai, Wang Yuanyuan, Zeng Xiangjun, Et al., Novel method of fault line selection based on characteristic analysis of transient phase-current, Proceedings of the CSU-EPSA, 29, 1, pp. 30-36, (2017)
  • [9] Wu Lepeng, Huang Chun, Lin Dabin, Et al., Faulty line selection based on transient wavelet energy for non-solid-earthed network, Electric Power Automation Equipment, 33, 5, pp. 70-75, (2013)
  • [10] Liang Rui, Cui Lianhua, Du Zhili, Et al., Fault line selection and location in distribution power network based on traveling wave time differece of arrival relationships, High Voltage Egineering, 40, 11, pp. 3411-3417, (2014)