Online Detection Method for Capacitor Voltage Transformer Measurement Error Adapted to Nonstationary Random Processes

被引:0
|
作者
Zhang, Zhu [1 ]
Lu, Heng [1 ]
Li, Binbin [2 ]
Qin, Shaorui [2 ]
Ding, Lijian [1 ]
机构
[1] Hefei Univ Technol, Sch Elect Engn & Automat, Hefei 230009, Peoples R China
[2] China & State Grid Anhui Elect Power Co, Elect Power Res Inst, Hefei 230601, Peoples R China
基金
中国国家自然科学基金;
关键词
Principal component analysis; Voltage measurement; Measurement errors; Data models; Measurement uncertainty; Kernel; Feature extraction; Accuracy; Transformers; Matrix decomposition; Capacitor voltage transformer (CVT); enhanced integrated principal component analysis (EIPCA); measurement error; modeling error; nonstationary random process; online detection;
D O I
10.1109/TIM.2024.3472842
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Capacitor voltage transformers (CVTs) are measurement devices widely used in high-voltage power grids, and the long-term stability of their measurement errors affects the safe operation of power systems. To address the problem of insufficient real-time periodic calibration using standard transformers, this article proposes an online detection method for CVT measurement error based on enhanced integrated principal component analysis (EIPCA). Considering that the secondary output voltage of CVTs is characterized by a nonstationary random distribution, the method combines the advantages of principal component analysis (PCA) and kernel principal component analysis (KPCA) to enhance its ability to process mixed linear and nonlinear data. It performs variational mode decomposition (VMD) of the linear residuals mapped in the cascade process to eliminate the modeling error caused by nonstationary data. Finally, the residual component characterizing the integrated error information of the CVT is separated from the primary voltage fluctuation, and the $T<^>{2}$ statistic is established as the index of measurement error detection. The experimental results show that the EIPCA-based online error detection method proposed in this article can effectively detect the 0.2-level error of the CVT, significantly improving detection performance compared with traditional PCA.
引用
收藏
页数:11
相关论文
共 25 条
  • [21] Multi-Synchrosqueezing Transform-Based Hybrid Method for Frequency Components Detection of Nonstationary Voltage and Current Waveforms
    Chang, Gary W.
    Noen, Bui Huu
    Sun, Gary H.
    Huang, Wei-Yun
    Yu, Johnson C.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 3630 - 3640
  • [22] Improved Extended EMF-Based Sensorless Control for IPMSMs With Small DC-Link Capacitor Considering DC-Link Voltage Measurement Error
    Yan, Jun
    Wu, Ximeng
    Zhu, Zi-Qiang
    Liu, Chaohui
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2024, 60 (04) : 6299 - 6313
  • [23] Online detection method of transformer winding deformation based on combined analysis of short circuit impedance and ΔU-I1 locus characteristics
    Li Z.
    Jiang W.
    Yu C.
    Chen X.
    Li Z.
    Xu Y.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (07): : 203 - 209and217
  • [24] Multi-probe method for straightness profile measurement based on least uncertainty propagation (1st report) Two-point method considering cross-axis translational motion and sensor's random error
    Okuyama, Eiki
    PRECISION ENGINEERING-JOURNAL OF THE INTERNATIONAL SOCIETIES FOR PRECISION ENGINEERING AND NANOTECHNOLOGY, 2010, 34 (01): : 49 - 54
  • [25] Multi-probe method for straightness profile measurement based on least uncertainty propagation (2nd report)-Two-point method considering cross-axis translational motion, pitch motion and sensor's random error
    Okuyama, Eiki
    Akata, Hirotake
    Ishikawa, Hiromi
    PRECISION ENGINEERING-JOURNAL OF THE INTERNATIONAL SOCIETIES FOR PRECISION ENGINEERING AND NANOTECHNOLOGY, 2010, 34 (04): : 683 - 691