Thermodynamic analysis of a solar powered ejector cooling system

被引:0
作者
Khennich, Mohammed [1 ]
Galanis, Nicolas [2 ]
Sorin, Mikhail [2 ]
Orfi, Jamel [3 ]
Sarrafi, Ahmadreza [1 ]
Dupuis, Serge [4 ]
机构
[1] Mechanical Engineering Department, Université de Moncton, Moncton, NB
[2] Mechanical Engineering Department, Université de Sherbrooke, Sherbrooke, QC
[3] Mechanical Engineering Department, King Saud University, Riyadh
[4] Civil Engineering Department, Université de Moncton, Moncton, NB
来源
International Journal of Thermofluids | 2024年 / 24卷
基金
加拿大自然科学与工程研究理事会;
关键词
Climate change mitigation; Coefficient of performance (COP); Ejector; Exergy efficiency; Parabolic trough collector; Solar powered cooling system;
D O I
10.1016/j.ijft.2024.100960
中图分类号
学科分类号
摘要
A steady-state model of an ejector cooling system activated by solar heat is presented and applied in response to the increasing demand of cooling in hot-climatic regions. The system comprises three loops connected by heat exchangers. The first loop, or collection sub-system, includes the solar collectors (both cylindrical-parabolic and flat plate collectors are modeled) and the heat transfer fluid (a thermal oil). The second loop also includes an ejector which uses polytropic efficiencies and provides the power necessary to circulate a second low-pressure stream of the refrigerant through the evaporator and an intermediate-pressure condenser. The third loop connects the load to the evaporator using ethylene glycol. In this study, the model is particularly based on the laws of classical and finite size thermodynamics and incorporates experimentally derived relations for the efficiency of the cylindrical-parabolic collectors as well as an ejector model which is based on physical laws rather than on refrigerant specific correlations used in previous studies. The results include a parametric study analysing the effect of the generator superheating and the calorific flow of the heat transfer fluid on the ejector dimensions and the overall system performance. The impact of the solar collector type on the collector surface and the system performance by a fixed incident radiation was investigated. The results illustrate that using parabolic trough collectors, the exergy efficiency of the entire system and the required collector's area are almost constant with the solar radiation intensity. They are approximately 35 % and 35 m2 respectively. It was also shown that further superheating the refrigerant by an additional 10 °C at the generator exit reduces the ejector's total length by 8.1 %, leading to positive economic impacts on raw material acquisition for the solar-powered ejector refrigeration system. Furthermore, doubling the calorific flow reduced the COP by half and increased the ejector length. The economic analysis of the system reveals two key findings: The largest portion of the initial costs is attributed to the solar collector, which is essential for providing the thermal energy required for the system's operation. The main hourly expense of the system is the electricity cost associated with powering the pumps. © 2024
引用
收藏
相关论文
共 50 条
  • [41] Solar powered combined ejector vapour compression cycle for air conditioning and refrigeration
    Sun, DW
    ENERGY CONVERSION AND MANAGEMENT, 1997, 38 (05) : 479 - 491
  • [42] Thermodynamic analysis and optimization of a CO2 based transcritical refrigeration system with an ejector
    Ahammed, Md. Ezaz
    Bhattacharyya, Souvik
    Ramgopal, Maddali
    DYNAMICS OF MACHINES AND MECHANISMS, INDUSTRIAL RESEARCH, 2014, 592-594 : 1825 - 1831
  • [43] A novel Kalina power-cooling cycle with an ejector absorption refrigeration cycle: Thermodynamic modelling and pinch analysis
    Rashidi, Jouan
    Yoo, ChangKyoo
    ENERGY CONVERSION AND MANAGEMENT, 2018, 162 : 225 - 238
  • [44] Thermodynamic analysis and optimization of a novel combined power and ejector refrigeration cycle - Desalination system
    Sadeghi, Mohsen
    Yari, Mortaza
    Mahmoudi, S. M. S.
    Jafari, Moharram
    APPLIED ENERGY, 2017, 208 : 239 - 251
  • [45] An investigation on the performance of solar ejector refrigeration system
    Zhang, B
    Shen, SQ
    ENERGY CONVERSION AND APPLICATION, VOL I AND II, 2001, : 1231 - 1234
  • [46] Thermodynamic assessments of the novel cascade air cooling system including solar heating and desiccant cooling units
    Caliskan, Hakan
    Hong, Hiki
    Jang, Jin Kyung
    ENERGY CONVERSION AND MANAGEMENT, 2019, 199
  • [47] Use of variable geometry ejector with cold store to achieve high solar fraction for solar cooling
    Dennis, M.
    Garzoli, K.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (07): : 1626 - 1632
  • [48] Thermodynamic analysis of a steam ejector chiller with ice storage
    Vaccaro, Guglielmo
    Milazzo, Adriano
    Socci, Luca
    Talluri, Lorenzo
    15TH IIR-GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS, 2022, : 743 - 750
  • [49] Efficiency analysis of alternative refrigerants for ejector cooling cycles
    Gil, Bartosz
    Kasperski, Jacek
    ENERGY CONVERSION AND MANAGEMENT, 2015, 94 : 12 - 18
  • [50] Analysis of a solar assisted vapour compression cooling system
    Chesi, Andrea
    Ferrara, Giovanni
    Ferrari, Lorenzo
    Tarani, Fabio
    RENEWABLE ENERGY, 2013, 49 : 48 - 52