OPTIMIZATION OF MIDDLE AND DEEP GROUND SOURCE HEAT PUMP HEATING SYSTEM BASED ON IMPROVED PARTICLE SWARM OPTIMIZATION ALGORITHM

被引:0
作者
Zhang J. [1 ]
Xu J. [2 ]
Xu J. [2 ]
Xin M. [1 ]
Zhang J. [1 ]
机构
[1] Northwest Engineering Corporation Limited, PowerChina, Xi’an
[2] Qinghai Branch of Powerchina Renewable Energy Co.,Ltd., Xining
[3] State Key Laboratory of Multiphase Flow in Power Engineering, Xi’an Jiaotong University, Xi’an
来源
Taiyangneng Xuebao/Acta Energiae Solaris Sinica | 2024年 / 45卷 / 04期
关键词
buried pipe; geothermal energy; ground source heat pump; improvement optimization; particle swarm optimization(PSO);
D O I
10.19912/j.0254-0096.tynxb.2022-1900
中图分类号
学科分类号
摘要
A middle and deep ground source heat pump heating system with variable operating conditions and a thermal storage device is constructed. Based on the improved particle swarm optimization algorithm,the operation of the system is optimized with the operating cost,system coefficient of performance(COP)and geothermal energy utilization coefficient as objective functions,and the optimization results are compared and analyzed. The results show that the operating cost,system COP and geothermal energy utilization coefficient are 279.27 yuan,6.4420 and 0.8527,respectively. Taking the system COP as the objective function ,the optimization effect is opposite to the operating cost,but similar to the geothermal energy utilization coefficient. © 2024 Science Press. All rights reserved.
引用
收藏
页码:311 / 317
页数:6
相关论文
共 10 条
  • [1] ZHANG B B., Study on energy efficiency of deep borehole casing type buried pipe heat exchanger and ground source side water system[D], (2019)
  • [2] REN Y Z., Experimental study on medium deep soil source heat pump system in severe cold area[D], (2019)
  • [3] DENG J W, LIANG M,, Et al., Field test on energy performance of medium- depth geothermal heat pump systems (MD- GHPs)[J], Energy and buildings, 184, pp. 289-299, (2019)
  • [4] ZUO T T, LI X L, WANG Z S., Application of medium-depth double U-tube ground-source heat pump systems to severe cold zone[J], Heating ventilating & air conditioning, 51, 12, pp. 119-123, (2021)
  • [5] DU S S,, ZHANG Y,, LIU X, Et al., Analysis of design load ratio of medium-depth geothermal heat pump systems with auxiliary heating in Northwest China[J], Northwest hydropower, 1, pp. 95-98, (2022)
  • [6] DIAO N R, FANG Z H., Ground- coupled heat pump technology[M], pp. 21-22, (2006)
  • [7] GORDON J M, CHUA H T., Centrifugal chillers:Thermodynamic modelling and a diagnostic case study[J], International journal of refrigeration, 18, 4, pp. 253-257, (1995)
  • [8] BERNIER M A,, BOURRET B., Pumping energy and variable frequency drives[J], ASHRAE journal, 41, 12, pp. 37-40, (1999)
  • [9] EBERHART R., Particle swarm optimization, Proceedings of ICNN’95-International Conference on Neural Networks, pp. 1942-1948, (2002)
  • [10] TANG X L., The theory and application of particle swarm optimization algorithm based on chaos[D], (2007)