Novel Four-Gas Fault Interpretation Graphical Technique for Mineral Oil Transformer

被引:2
作者
Patil, Atul Jaysing [1 ,2 ]
Naresh, Ram [1 ,2 ]
Jarial, Raj Kumar [1 ,2 ]
Malik, Hasmat [3 ]
机构
[1] NIT Hamirpur, Elect Dept, Hamirpur 177005, India
[2] NIT Hamirpur, TIFAC Core Lab, Hamirpur 177005, India
[3] UTM Univ, Elect Dept, Johor Baharu 81310, Malaysia
关键词
Oil insulation; Fault diagnosis; Gases; Transformers; Power transformer insulation; Oils; Minerals; Diagnostic tools; geometrical diagnostic methods; mineral oil; transformer fault diagnosis; DISSOLVED-GAS ANALYSIS; IEC TC 10; INCIPIENT FAULTS; DIAGNOSIS; DGA;
D O I
10.1109/TDEI.2024.3381093
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Ensuring transformer health and accurate fault diagnosis is pivotal for the reliable operation of power system network. Traditional incipient fault diagnostic methods, including DP-1, DP-2, DT-1, DT-4, and IEC, have been employed extensively, but with varied levels of accuracy for different fault categories. In this research, authors introduce a four-gas diagnostic method, an innovative graphical approach that emphasizes analyzing only four gases, with satisfactory diagnostic accuracy while ensuring lower computational burden and higher interpretability. By adopting a set of two equations for graphically determining fault category, the method offers an intuitive understanding of incipient faults in an oil-filled transformer. For this study, a total of 963 different transformer DGA data were utilized. A study was undertaken using the IEC TC 10 database results to assess the effectiveness of the proposed diagnostic method across diverse fault categories. The proposed 4GM method achieved an execution time of 1.46 s, demonstrating better performance in detecting discharge and high thermal faults, while its efficacy in identifying low thermal faults was slightly depleted. The proposed 4GM method stands out as it achieves a balance between accuracy and execution time. This research not only offers insights into the strengths and innovations of the 4GM method but also sets the stage for future advancements in transformer diagnostic techniques.
引用
收藏
页码:2721 / 2730
页数:10
相关论文
共 31 条
[1]   A Review of Dissolved Gas Analysis Measurement and Interpretation Techniques [J].
Abu Bakar, Norazhar ;
Abu-Siada, A. ;
Islam, S. .
IEEE ELECTRICAL INSULATION MAGAZINE, 2014, 30 (03) :39-49
[3]  
[Anonymous], 2019, IEEE Standard C57.104
[4]  
[Anonymous], 2022, IEC 60599
[5]  
[Anonymous], 2003, Transformer Diagnostics, V3-31
[6]   Power transformer fault diagnosis based on dissolved gas analysis by support vector machine [J].
Bacha, Khmais ;
Souahlia, Seifeddine ;
Gossa, Moncef .
ELECTRIC POWER SYSTEMS RESEARCH, 2012, 83 (01) :73-79
[7]   Neuro fuzzy schemes for fault detection in power transformer [J].
Duraisamy, V. ;
Devarajan, N. ;
Somasundareswari, D. ;
Vasanth, A. Antony Maria ;
Sivanandam, S. N. .
APPLIED SOFT COMPUTING, 2007, 7 (02) :534-539
[8]   Interpretation of gas-in-oil analysis using new IEC publication 60599 and IEC TC 10 databases [J].
Duval, M ;
dePablo, A .
IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (02) :31-41
[9]  
Duval M, 2014, IEEE ELECTR INSUL M, V30, P9, DOI 10.1109/MEI.2014.6943428
[10]   Two Graphical Shapes Based on DGA for Power Transformer Fault Types Discrimination [J].
Emara, Manal M. ;
Peppas, Georgios D. ;
Gonos, Ioannis F. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (03) :981-987