RESEARCH ON CONTROL STRATEGY OF GRID-CONNECTED INVERTER BASED ON PARAMETER ADAPTIVE ADJUSTMENT OF VIRTUAL SYNCHRONOUS GENERATOR

被引:0
作者
He, Xin [1 ]
Zuo, Yunpei [2 ]
Yang, Yinghai [2 ]
Liu, Cui [2 ]
Zhou, Xin [1 ]
Wang, Delin [2 ]
机构
[1] Electric Power Research Institute, Yunnan Power Grid Co.,Ltd., Kunming
[2] School of Electrical Engineering, Southwest Jiaotong University, Chengdu
来源
Taiyangneng Xuebao/Acta Energiae Solaris Sinica | 2024年 / 45卷 / 07期
关键词
adaptive control systems; damping; grid-connected inverters; virtual inertia; virtual synchronous generator;
D O I
10.19912/j.0254-0096.tynxb.2023-0496
中图分类号
学科分类号
摘要
After the integration of new energy sources with typical characteristics of small inertia and weak damping" into power grid,the active power of AC bus will experience severe fluctuations when the power system is disturbed,leading a potential threat to the frequency stability of power grid. Therefore,an improved parameter adaptive control strategy based on virtual synchronous generator (VSG)is proposed in this paper. Firstly,controlling the inverter to operate in VSG mode and making the virtual inertia and damping parameters associate with the deviation and rate of change of VSG output angular frequency during operation,in order to achieve the aim of smoothing frequency fluctuations. Then,in order to avoid unnecessary noise interference caused by the derivative operation in adaptive control upon the system,further adaptive optimization control is carried out on the inverter,replacing angular frequency derivative term in the original control link with power deviation,as simplify the control link,and improve the dynamic regulation waveform of grid frequency. Finally,the correctness of the proposed adaptive control strategy was proved through simulation examples,and the effectiveness of the presented strategy in suppressing active power and frequency fluctuations under disturbances was verified. © 2024 Science Press. All rights reserved."
引用
收藏
页码:259 / 266
页数:7
相关论文
共 18 条
  • [1] ZHAO E S,, HAN Y, ZHOU S Y,, Et al., Review and prospect of inertia and damping simulation technologies of microgrids[J], Proceedings of the CSEE, 42, 4, pp. 1413-1427, (2022)
  • [2] XIE X R, MAO H Y,, Et al., New issues and classification of power system stability with high shares of renewables and power electronics[J], Proceedings of the CSEE, 41, 2, pp. 461-475, (2021)
  • [3] YIN G L, DONG H, DAI Y C,, Et al., Adaptive control strategy of VSG parameters in photovoltaic microgrid[J], Power system technology, 44, 1, pp. 192-199, (2020)
  • [4] ZHENG T W, CHEN L J,, CHEN T Y, Et al., Review and prospect of virtual synchronous generator technologies[J], Automation of electric power systems, 39, 21, pp. 165-175, (2015)
  • [5] GU R Z., Research on inverter and grid-connected control of wind/PV/battery microgrid[D], (2019)
  • [6] MAO F B,, ZHANG X,, LIU F,, Et al., Research on improved VSG control strategy based on virtual damping compensation[J], Power electronics, 50, 9, pp. 75-78, (2016)
  • [7] REN H P,, CHEN Q, ZHANG L L,, Et al., Parameter adaptive strategy for virtual synchronous generator control [J], Control theory & applications, 37, 12, pp. 2571-2580, (2020)
  • [8] MIAO H Y, YANG Y,, MEI F,, Et al., A seamless mode switching control strategy in virtual synchronous generator [J], Acta energiae solaris sinica, 41, 9, pp. 121-128, (2020)
  • [9] LIU H, SONG P,, Et al., Influence of voltage loop on stability of photovoltaic virtual synchronous generators[J], Acta energiae solaris sinica, 42, 3, pp. 311-318, (2021)
  • [10] WEI X, Et al., Improved droop control strategy for parallel operation of cascaded power electronic transformers[J], High voltage engineering, 47, 4, pp. 1274-1282, (2021)