Electric Field Features and Charge Behavior in Oil-Pressboard Composite Insulation under Impulse Voltage

被引:0
|
作者
Deng, Jun [1 ]
Gao, Chunjia [2 ]
Xie, Zhicheng [1 ]
Ge, Hao [2 ]
Zhou, Haibin [1 ]
Zhao, Xiaolin [2 ]
Pan, Zhicheng [1 ]
Qi, Bo [2 ]
机构
[1] China Southern Power Grid EHV Power Transmiss Co, Guangzhou 510405, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewable, Beijing 102206, Peoples R China
关键词
impulse voltage; oil-pressboard/paper insulation; electric field measurement; charge migration model;
D O I
10.3390/en17194903
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Oil-pressboard/paper insulation materials are essential in transformers for ensuring their safe and stable operation, primarily due to their roles in spatial electric field distribution and charge migration mechanisms. Current spatial distribution analyses rely on computational methods that lack empirical validation, particularly for oil-pressboard/paper composites. This study leverages the principles of the Kerr electro-optic effect to develop a rapid measurement platform for electric fields within oil-pressboard/paper insulation under impulse voltage conditions, which measures the spatial electric field characteristics using Cu-Cu and Al-Al electrodes under various scenarios: with asymmetric and symmetric pressboard coverage and different numbers of insulating paper layers. Findings indicated: (1) In asymmetric pressboard models, Cu-Cu electrodes exhibit a consistent peak electric field of approximately 16 kV/mm, while Al-Al electrodes show peak values of 18.13 kV/mm and -14.98 kV/mm. Charge density patterns are similar, with Cu-Cu at about 68 mu C/m2 and Al-Al at 11.2 mu C/m2 and -124.8 mu C/m2. (2) Symmetric models present consistent peak electric fields and charge densities for both polarities. (3) Increasing insulating paper layers elevates electric field strengths. Both electrodes show the similar peak field of about 17 kV/mm with differing paper layers due to higher charge injection from the Al electrode. (4) Utilizing the Schottky effect and field emission principles, the study clarifies charge generation and migration mechanisms. These insights could provide a theoretical foundation for designing and verifying oil-pressboard/paper insulation structures in transformers.
引用
收藏
页数:18
相关论文
共 50 条
  • [1] Transient Electric Field Characteristics in Oil-Pressboard Composite Insulation under Voltage Polarity Reversal
    Qi, Bo
    Zhao, Xiaolin
    Li, Chengrong
    Wu, Hao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (04) : 2148 - 2155
  • [2] Influence of moisture on the interface charge of oil-pressboard composite insulation under DC voltage
    Qi, Bo
    Jiao, Yanqiu
    Gao, Chunjia
    Zhang, Shuqi
    Zhao, Xiaolin
    Li, Chengrong
    HIGH VOLTAGE, 2018, 3 (01): : 73 - 77
  • [3] Polarity Characteristics of Accumulated Charge in Oil-pressboard Composite Insulation Under DC Voltage
    Zhuang Y.
    Wang Y.
    Wei X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (23): : 8791 - 8802
  • [4] Influence of Pressboard Orientation in the Electric Field on Lightning Impulse Discharge Characteristics of Oil-Pressboard Insulation
    Li, Jiansheng
    Wei, Chao
    Wu, Yiming
    Wang, Shengquan
    Lin, Yuandi
    Huang, Leifeng
    Li, Houying
    Wang, Youyuan
    2019 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2019, : 275 - 278
  • [5] Influencing mechanism of temperature on the electric field distribution and interface charge accumulation in oil-pressboard insulation under DC voltage
    Gao, Chunjia
    Ge, Hao
    Yuan, Qing
    Wu, Juzhen
    Cao, Yanming
    Tian, Huidong
    Qi, Bo
    Li, Chengrong
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2025, 58 (11)
  • [6] Breakdown Characteristics of the Oil-Pressboard Insulation under Compound Electric Field
    Chi, M. H.
    Chen, Q. G.
    Liu, H. L.
    Gao, Y.
    Wei, X. L.
    Wang, Y. H.
    Chi, Y.
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 817 - 821
  • [7] Interface Charge Polarity Effect Based Analysis Model for Electric Field in Oil-pressboard Insulation under DC Voltage
    Qi, Bo
    Gao, Chunjia
    Zhao, Xiaolin
    Li, Chengrong
    Wu, Hao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (05) : 2704 - 2711
  • [8] HVDC Electric Field Control by Pressboard Arrangement in Oil-Pressboard Composite Electrical Insulation Systems
    Okubo, H.
    Sakai, T.
    Furuyashiki, T.
    Takabayashi, K.
    Kato, K.
    2016 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2016, : 35 - 39
  • [9] Discharge characteristics of oil-pressboard insulation under impulse voltage waveforms with different parameters
    Wang, Zhe
    Zhang, Qiaogen
    Wang, Tonglei
    Li, Jinzhong
    Gaodianya Jishu/High Voltage Engineering, 2015, 41 (06): : 1974 - 1980
  • [10] Impact of interfacial charge of oil-pressboard insulation on surface flashover voltage under compound AC-DC electric field
    Chen, Yilong
    Qi, Bo
    Li, Chengrong
    Xi, Chaochao
    Dianwang Jishu/Power System Technology, 2014, 38 (04): : 1070 - 1075