Experimental investigation on the vented flame and pressure behaviour of hydrogen-air mixtures

被引:0
|
作者
Sheng, Yuhuai [1 ]
Luo, Zhenmin [1 ,2 ,3 ]
Liu, Litao [1 ]
Yang, Zhe [1 ]
Meng, Fan [1 ]
Dong, Zhe [1 ]
Zhang, Yanni [1 ]
Qu, Jiao [1 ]
Deng, Jun [4 ]
Wang, Tao [1 ,2 ,3 ]
机构
[1] Xian Univ Sci & Technol, Sch Safety Sci & Engn, 58 Yanta Mid Rd, Xian 710054, Shaanxi, Peoples R China
[2] Xian Key Lab Urban Publ Safety & Fire Rescue, 58 Yanta Mid Rd, Xian 710054, Shaanxi, Peoples R China
[3] Shaanxi Engn Res Ctr Ind Proc Safety & Emergency R, 58 Yanta Mid Rd, Xian 710054, Shaanxi, Peoples R China
[4] Shaanxi Key Lab Prevent & Control Coal Fire, 58 Yanta Mid Rd, Xian 710054, Shaanxi, Peoples R China
基金
中国国家自然科学基金;
关键词
Hydrogen-air; Deflagration venting; Secondary explosion; Static activation pressure; Flame propagation; BURST PRESSURE; GAS-EXPLOSIONS; DEFLAGRATIONS; IGNITION; VESSEL; OVERPRESSURES; DUCT;
D O I
10.1016/j.jlp.2024.105469
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
To explore the changes in pressure and flame propagation inside and outside the vessel when the pipe diameter does not match the vent diameter, and to check the conservatism of standards NFPA 68 and EN 14491 for this case, an experimental apparatus was utilized to investigate the influences of static activation pressure (0.7-1.75 bar) and vent diameter (30-70 mm) on the deflagration behavior of hydrogen-air mixtures (Phi: 0.6-1.4). The vented pressure, flame propagation, and pressure-flame interaction characteristics of hydrogen-air mixtures were observed and analyzed. Additionally, the conservatism of the calculated venting area under the experimental conditions of NPFA 68 and EN 14491 was verified. The results indicated that under an equivalence ratio of 0.6, the pressure-time curve inside the container exhibited only one peak (Pmax11). In the stoichiometric and fuel-rich states, the pressure-time curve inside the container exhibited two peaks attributed to the decrease in venting efficiency due to the secondary explosion inside the pipe, increasing the turbulence intensity within the container. When the static activation pressure is 0.7 bar, the pressures of the three vent diameters of 30, 50 and 70 dropped by 11.34%, 24.38% and 26.86% respectively. And the Pmax11 at Phi = 1.0 and Phi = 1.4 are similar, while this phenomenon is not observed for other vent diameters. When the vent diameter was inconsistent with the duct diameter. the calculations of both standards were conservative. However, under these testing conditions (vent diameter: 30-70 mm, static activation pressure: 0.7-1.75 bar), the NPFA 68 calculations yield a conservatism range of 3.3-11, whereas EN14491 ranges from 1.6 to 15.7. The NPFA 68 results were more stable and concentrated, making these conditions more suitable for industry safety design in hydrogen venting.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Flame propagation in stratified hydrogen-air mixtures: Spark placement effects
    Owston, Rebecca
    Abraham, John
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2009, 34 (15) : 6532 - 6544
  • [32] ANALYTICAL AND NUMERICAL MODELING OF FLAME-BALLS IN HYDROGEN-AIR MIXTURES
    BUCKMASTER, J
    SMOOKE, M
    GIOVANGIGLI, V
    COMBUSTION AND FLAME, 1993, 94 (1-2) : 113 - 124
  • [33] An analysis of flame instabilities for hydrogen-air mixtures based on Sivashinsky equation
    Yanez, J.
    Kuznetsov, M.
    PHYSICS LETTERS A, 2016, 380 (33) : 2549 - 2560
  • [34] Investigation of dominant parameters for flame structure of hydrogen-air premixed flame with curvature
    Arai, Yasushi
    Hayashi, Naoki
    Yamashita, Hiroshi
    Nihon Kikai Gakkai Ronbunshu, B Hen/Transactions of the Japan Society of Mechanical Engineers, Part B, 2013, 79 (807): : 2486 - 2496
  • [35] Vented hydrogen-air deflagration in a small enclosed volume
    Rocourt, X.
    Awamat, S.
    Sochet, I.
    Jallais, S.
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2014, 39 (35) : 20462 - 20466
  • [36] Effect of vent size on vented hydrogen-air explosion
    Zhang, Sihong
    Zhang, Qi
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2018, 43 (37) : 17788 - 17799
  • [37] Effect of ignition position on vented hydrogen-air explosions
    Guo, Jin
    Sun, Xuxu
    Rui, Shengchao
    Cao, Yong
    Hu, Kunlun
    Wang, Changjian
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2015, 40 (45) : 15780 - 15788
  • [38] External overpressure of vented hydrogen-air explosion in the tube
    Cao, Yong
    Wang, Yongxu
    Song, Xianzhao
    Xing, Huadao
    Li, Bin
    Xie, Lifeng
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2019, 44 (60) : 32343 - 32350
  • [39] EXPERIMENTAL INVESTIGATION OF COMBUSTION OF A LIQUID-HYDROCARBON FUEL, ATOMIZED IN A DIFFUSION HYDROGEN-AIR FLAME
    ANNUSHKIN, YM
    MASLOV, GF
    COMBUSTION EXPLOSION AND SHOCK WAVES, 1981, 17 (05) : 509 - 513
  • [40] Large scale experiment of a roof vented deflagration of high-concentration hydrogen-air mixtures
    Yoon, Ung-Gi
    Park, Byoungjik
    Kim, Wookyung
    Kim, Yangkyun
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2024, 184 : 1411 - 1423