Cascade control mode of indoor temperature PIλDµ and supply air temperature PDµ for multi-evaporator air-conditioning system

被引:0
|
作者
Wei, Ming-Song [1 ]
Li, Shao-Yong [1 ]
Zhou, Jiao [2 ]
Wang, Cheng-Min [1 ]
Yang, Rui [1 ]
机构
[1] School of Civil Engineering, Lanzhou University of Technology, Gansu, Lanzhou,730050, China
[2] School of Civil Engineering, Tianshui Normal University, Gansu, Tianshui,741000, China
来源
Kongzhi Lilun Yu Yingyong/Control Theory and Applications | 2024年 / 41卷 / 10期
基金
中国国家自然科学基金;
关键词
Adaptive control systems - HVAC - Indoor air pollution - Linear programming - Optimal control systems - Proportional control systems - Relay control systems - Three term control systems - Two term control systems - Window screens;
D O I
10.7641/CTA.2023.20686
中图分类号
学科分类号
摘要
Aiming at regulating performance parameters of the multi evaporator air-conditioning system (MEACS), this project proposes a cascade control mode of indoor temperature PIλDµ and supplys air temperature PDµ and an improved multi-objective artificial fish swarm algorithm (IMOAFSA) is designed to tune parameters of fractional order PID controller for indoor temperature (IT-FOPIDC) and fractional order PD controller for supply air temperature (SAT-FOPDC), so as to stabilize the state point of supply air of MEACS and improve the regulation quality of indoor temperature. Firstly, according to the basic single objective artificial fish swarm algorithm (BSOAFSA), an adaptive factor is constructed to execute the nonlinear decreasing evolution to the visual field and step size in the fish swarm, so an improved single objective artificial fish swarm algorithm (ISOAFSA) is rebuilt. Secondly, on the basis of this ISOAFSA, Gaussian variation is introduced into external files (EF) to design an improved multi-objective artificial fish swarm algorithm (IMOAFSA) in order to continuously tune eight parameters of IT-FOPIDC and SAT-FOPDC. Finally, the control effects hosted by this cascade control system for indoor temperature and supply air temperature are numerically simulated. The results show that the designed IMOAFSA finds out Pareto optimal solutions (POS) of eight parameters of these two controllers and continuously updates them, which can obviously reduce fluctuation of supply air temperature and further improve the control quality of indoor temperature such as minor steady-state error, the smaller overshoot, the appropriate damping ratio and the shorter adjustment time, etc. © 2024 South China University of Technology. All rights reserved.
引用
收藏
页码:1842 / 1852
相关论文
共 50 条
  • [31] Robust Cascade Control System Design for Central Air-conditioning System
    Wang, Jiangjiang
    Jing, Youyin
    Zhang, Chunfa
    2008 7TH WORLD CONGRESS ON INTELLIGENT CONTROL AND AUTOMATION, VOLS 1-23, 2008, : 1506 - 1511
  • [32] Climate Compensation and Indoor Temperature Optimal Measuring Point Energy Saving Control in VAV Air-Conditioning System
    Yan, Xiuying
    Liu, Cong
    Li, Meili
    Hou, Ating
    Fan, Kaixing
    Meng, Qinglong
    ENERGIES, 2019, 12 (22)
  • [33] Analysis of comfort and energy-consumption on temperature control air-conditioning system
    Yang, C.-Z. (yang0369@126.com), 1600, Hunan University (39):
  • [34] Study on Load Distribution of Temperature and Humidity Independent Control Air-Conditioning System
    Ouyang, Qin
    Xiang, Liping
    Ouyang, Min
    PROCEEDINGS OF THE 2015 ASIA-PACIFIC ENERGY EQUIPMENT ENGINEERING RESEARCH CONFERENCE (AP3ER 2015), 2015, 9 : 79 - 82
  • [35] Automatic temperature and humidity control system using air-conditioning in transformer substation
    Feng, Li
    Hui, Zhou
    Yan, Tao
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [36] Model-based robust temperature control for VAV air-conditioning system
    Huang, Gongsheng
    Jordan, Fillip
    HVAC&R RESEARCH, 2012, 18 (03): : 432 - 445
  • [37] Performance of temperature and humidity independent control air-conditioning system in an office building
    Zhao, Kang
    Liu, Xiao-Hua
    Zhang, Tao
    Jiang, Yi
    ENERGY AND BUILDINGS, 2011, 43 (08) : 1895 - 1903
  • [38] Performance comparison of temperature and humidity independent control air-conditioning system with conventional system
    Zhang, Tao
    Liu, Xiao-Hua
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2016, 37 (04): : 479 - 488
  • [39] Air-conditioning system by stored snow .1. Control system of air temperature/humidity and its performance
    Kobiyama, M
    Wang, A
    Takahashi, T
    Yoshinaga, H
    Kawamoto, S
    Iijima, K
    SNOW ENGINEERING: RECENT ADVANCES, 1997, : 559 - 563
  • [40] Design and implementation of humanized temperature control for hotel air-conditioning
    Li Zhi
    MATERIAL SCIENCE, CIVIL ENGINEERING AND ARCHITECTURE SCIENCE, MECHANICAL ENGINEERING AND MANUFACTURING TECHNOLOGY II, 2014, 651-653 : 684 - 687