Performance evaluation of a central air conditioning system using condensate as a discharge line cooler

被引:0
|
作者
Sumeru, Kasni [1 ]
Pramudantoro, Triaji Pangripto [1 ]
Badarudin, Apip [1 ]
Setyawan, Andriyanto [1 ]
Sumeru, Husain Akbar [2 ]
bin Sukri, Mohamad Firdaus [3 ]
Sulaimon, Shodiya [4 ]
机构
[1] Politeknik Negeri Bandung, Dept Refrigerat & Air Conditioning, Gegerkalong Hilir Ciwaruga, Bandung 40012, Indonesia
[2] Univ Padjadjaran, Dept Chem Ind Technol, Sumedang 45363, Indonesia
[3] Univ Teknikal Malaysia Melaka, Fac Mech Technol & Engn, Durian Tunggal 76100, Melaka, Malaysia
[4] Univ Maiduguri UNIMAID, Dept Mech Engn, Borno, Nigeria
关键词
Condensate; Cooling capacity; Discharge line; DX system; COP improvement; INTERNAL HEAT-EXCHANGER; WATER; NANOPARTICLES; DESIGN; PLANT; R134A; SIO2;
D O I
10.1016/j.csite.2024.105310
中图分类号
O414.1 [热力学];
学科分类号
摘要
The energy consumption by central air conditioning (A/C) in a building is very high and efforts to reduce this energy consumption is ongoing. This study investigates the use of condensate produced by the evaporator inside the air handling unit (AHU) to cool the compressor discharge line. A central A/C with a direct expansion (DX) system and a compressor capacity of about 25 HP which uses R22 as a working fluid was used. The discharge line has a diameter of 15.9 mm wrapped with a 520 mm long heat exchanger with diameter 50 mm. The condensate produced by the AHU is passed to the heat exchanger that envelops the discharge line. The use of discharge line cooler could reduce the input power from 18.21 kW to 17.54 kW. On the other hand, the cooling capacity increased from 46.44 kW to 49.11 kW. This means that discharge cooler reduces the input power by 3.8 % and increases the cooling capacity by 5.7 %. As a result, the COP increases by 9.8 %, from 2.5 to 2.8. The method developed is not complex and only simple modification is required, thus an improvement of the performance of a central A/C system can be achieved.
引用
收藏
页数:11
相关论文
共 50 条
  • [21] Experimental Study on the Performance of an Air Conditioning Unit with a Baffled Indirect Evaporative Cooler
    Kim, Seong-Bhin
    Moon, Kwang-Am
    Choi, Hwi-Ung
    Choi, Kwang-Hwan
    ENERGIES, 2024, 17 (13)
  • [22] Performance evaluation of an air conditioning system based on quasi isothermal dehumidifcation
    Jagirdar, Mrinal
    Pandelidis, Demis
    Pacak, Anna
    Worek, William
    Cetin, Sabri
    ENERGY CONVERSION AND MANAGEMENT, 2020, 217
  • [23] Performance evaluation of an integrated automotive air conditioning and heat pump system
    Hosoz, M
    Direk, M
    ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (05) : 545 - 559
  • [24] Experimental study on improved performance of an automotive CO2 air conditioning system with an evaporative gas cooler
    Song, Xia
    Yuan, Haorui
    Zhang, Yun
    Yu, Binbin
    Wang, Dandong
    Shi, Junye
    Chen, Jiangping
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 140 : 39 - 48
  • [25] Effects of Sub-cooler on Cooling Performance of Air Conditioning System with Natural Refrigerant R290
    Cakraditya, Gavin
    Yudhi, Fathurrahman
    Yatim, Ardiyansyah
    INTERNATIONAL CONFERENCE ON SCIENCE AND APPLIED SCIENCE (ICSAS2020), 2020, 2296
  • [26] Exergoeconomic model of a central air conditioning system
    Avsyukevich, D. A.
    MAGAZINE OF CIVIL ENGINEERING, 2016, 67 (07): : 22 - 30
  • [28] Performance evaluation of absorption cooling system for air conditioning-based novel trigeneration system using solar energy
    Mishra, Shobhit
    Singh, Raj Kumar
    JOURNAL OF THE BRAZILIAN SOCIETY OF MECHANICAL SCIENCES AND ENGINEERING, 2024, 46 (06)
  • [29] Performance characterization of a small-capacity thermoacoustic cooler for air-conditioning applications
    Insu Paek
    Luc Mongeau
    James E. Braun
    Journal of Mechanical Science and Technology, 2010, 24 : 1781 - 1791
  • [30] A RADIANT AIR-CONDITIONING SYSTEM USING SOLAR-DRIVEN LIQUID DESICCANT EVAPORATIVE WATER COOLER
    Abdalla, S. A.
    Abdalla, Kamal N.
    JOURNAL OF ENGINEERING SCIENCE AND TECHNOLOGY, 2006, 1 (02) : 139 - 157