Analysis of structural improvement and potential energy recovery in the rain zone of natural draft wet cooling tower

被引:1
作者
Wang, Zhanpeng [1 ]
Zhang, Wenjie [2 ]
Tong, Shuaiwen [1 ]
Wei, Huimin [1 ]
机构
[1] North China Elect Power Univ, Key Lab Power Stn Energy Transfer Convers & Syst, Minist Educ, Beijing 102206, Peoples R China
[2] China Nucl Power Engn Co Ltd, Beijing, Peoples R China
关键词
Natural draft wet cooling tower; Dry-wet hybrid rain zone; High-level water collecting natural draft wet; cooling tower; Potential energy recovery; Crosswind; THERMAL PERFORMANCE; VENTILATION PERFORMANCE; NUMERICAL-SIMULATION; FIELD-TEST; LAYOUT; FLOW;
D O I
10.1016/j.icheatmasstransfer.2024.108268
中图分类号
O414.1 [热力学];
学科分类号
摘要
To address the issues of mismatched resistance and heat transfer characteristics in the rain zone of natural draft wet cooling towers (NDWCT), as well as the insufficient utilization of potential energy, this paper proposes a potential energy recovery model. This model quantifies the recoverable potential energy in the rain zone based on the distribution characteristics of water droplets in the NDWCT. The recovered energy is then used to drive fans, improving both the resistance and heat transfer performance of the NDWCT. Using the NDWCT of a 1000 MW nuclear power unit as the research object, eight types of water collection plates with a coverage rate of 25 % were designed. These plates are used to collect circulating water to drive water turbines, which in turn power the fans. Calculations show that all designs can recover more than 450 kW of potential energy from falling water. After determining the recoverable potential energy, the thermal performance of NDWCT, HNDWCT (High-level water collecting natural draft wet cooling tower), NDWCT with dry-wet hybrid rain zone, and NDWCT with both dry-wet hybrid rain zone and potential energy recovery was compared under different environmental crosswind conditions. The results show that the performance of HNDWCT declines sharply under higher crosswind speeds. When the crosswind speed reaches 8 m/s, its heat exchange capacity decreases by 51.6 % compared to windless conditions, leaving it at only 63.1 % of the heat exchange capacity of NDWCT, with an outlet water temperature 3.66 degrees C higher than that of NDWCT. In contrast, the cooling tower modified with the dry-wet hybrid rain zones and potential energy recovery technology was less affected by crosswinds, with cooling capacity reductions of 5.4 % and 10.3 % at 4 m/s and 8 m/s crosswinds, respectively, whereas NDWCT exhibited reductions of 7.1 % and 11.1 %. Additionally, the former demonstrated superior performance under all crosswind conditions, the outlet water temperatures under windless, 4 m/s, and 8 m/s crosswind conditions decreased by 0.49 degrees C, 0.65 degrees C, and 0.53 degrees C, respectively, with heat exchange capacity improvements of 4.4 %, 6.3 %, and 5.3 %. Compared to traditional dry-wet hybrid rain zone towers, the cooling tower with the dry-wet hybrid rain zones and potential energy recovery technology is less affected by environmental crosswinds. The outlet water temperature decreased by 0.11 degrees C, 0.2 degrees C, and 0.17 degrees C under windless, 4 m/s, and 8 m/s wind conditions, respectively.
引用
收藏
页数:16
相关论文
共 36 条
  • [1] CFD simulation of wet cooling towers
    Al-Waked, R
    Behnia, M
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (04) : 382 - 395
  • [2] Experimental investigation on thermal performance of natural draft wet cooling towers employing an innovative wind-creator setup
    Alavi, Seyed Rashid
    Rahmati, Mehdi
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 122 : 504 - 514
  • [3] Critical guidelines to cope with the adverse impacts of the inner peripheral vortex in the high-level water collecting natural draft wet cooling tower
    Chen, Guangan
    Zhao, Yuanbin
    Ge, Wenjing
    Li, Wendong
    [J]. APPLIED THERMAL ENGINEERING, 2020, 168
  • [4] A sensitivity-coefficients method for predicting thermal performance of natural draft wet cooling towers under crosswinds
    Chen, Kun
    Sun, Fengzhong
    Zhang, Lei
    Chen, Xuehong
    Zhang, Xiaoyu
    [J]. APPLIED THERMAL ENGINEERING, 2022, 206
  • [5] A novel layout of air-cooled condensers to improve thermo-flow performances
    Chen, Lei
    Yang, Lijun
    Du, Xiaoze
    Yang, Yongping
    [J]. APPLIED ENERGY, 2016, 165 : 244 - 259
  • [6] Numerical study regarding cooling capacity for non-equidistant fillings in large-scale wet cooling towers
    Chen, Rui
    Zhang, Deying
    Zhang, Zhengqing
    Han, Qiang
    He, Suoying
    Gao, Ming
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2021, 26 (26)
  • [7] Field test study on water droplet diameter distribution in the rain zone of a natural draft wet cooling tower
    Chen, Xuehong
    Sun, Fengzhong
    Lyu, Dongqiang
    [J]. APPLIED THERMAL ENGINEERING, 2019, 162
  • [8] New retrofit method to improve the thermal performance of natural draft wet cooling towers based on the reconstruction of the aerodynamic field
    Chen, Xuehong
    Sun, Fengzhong
    Chen, Youliang
    Gao, Ming
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 132 : 671 - 680
  • [9] Crosswind influence on cooling capacity in different zones for high level water collecting wet cooling towers based on field test
    Dang, Zhigang
    Gao, Ming
    Long, Guoqing
    Zou, Jian
    He, Suoying
    Sun, Fengzhong
    [J]. JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2019, 190 : 134 - 142
  • [10] Numerical simulation of thermal performance for super large-scale wet cooling tower equipped with an axial fan
    Dang, Zhigang
    Zhang, Zhengqing
    Gao, Ming
    He, Suoying
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 135 : 220 - 234