Investigation on Performance of Internally Cooled Liquid Desiccant Dehumidifier Based on ANN Model

被引:0
|
作者
Luo, Yimo [1 ]
Chang, Yayin [1 ]
Li, Nianping [1 ]
机构
[1] College of Civil Engineering, Hunan University, Changsha
来源
Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences | 2024年 / 51卷 / 09期
关键词
liquid desiccant dehumidifier; machine learning; neural networks(NN); parameterization investigation;
D O I
10.16339/j.cnki.hdxbzkb.2024100
中图分类号
学科分类号
摘要
Liquid desiccant dehumidifiers have received widespread attention due to their ability to utilize low-grade thermal energy and high dehumidification efficiency. However,the prediction accuracy of their mass transfer performance still needs to be improved. This article built up an experimental platform of a single-channel internally cooled liquid desiccant dehumidifier to study the effects of different parameters on its mass transfer efficiency. Meanwhile,an artificial neural network(ANN)model was established with MATLAB to predict the mass transfer efficiency of the dehumidifier. The ANN model was verified and validated with the above experimental data. The results indicated that the a mean absolute relative difference(MARD)between the predicted Sh of the ANN model and the experimental Sh was 4.07%. Compared with existing empirical formulas,the ANN model established in this paper had higher prediction accuracy. In addition,this article also used the ANN model to study the trend of Sh under different parameter changes,thereby investigating the impact of different parameters on the dehumidification performance. © 2024 Hunan University. All rights reserved.
引用
收藏
页码:198 / 205
页数:7
相关论文
共 24 条
  • [21] WEN T,LU L., Numerical and experimental study on internally cooled liquid desiccant dehumidification concerning film shrinkage shape and vapor condensation[J], International Journal of Thermal Sciences, 136, pp. 316-327, (2019)
  • [22] ZHANG X S,, PENG D G, Model validation and case study on internally cooled/heated dehumidifier/regenerator of liquid desiccant systems[J], International Journal of Thermal Sciences, 48, 8, pp. 1664-1671, (2009)
  • [23] WANG H H., An analytical model for heat and mass transfer processes in internally cooled or heated liquid desiccant-air contact units[J], International Journal of Heat and Mass Transfer, 50, 17, pp. 3545-3555, (2007)
  • [24] MESQUITA L C S,, HARRISON S J,, THOMEY D., Modeling of heat and mass transfer in parallel plate liquid-desiccant dehumidifiers, Solar Energy, 80, 11, pp. 1475-1482, (2006)