Load Control Using Sensitivity Identification by Means of Smart Transformer

被引:67
作者
De Carne, Giovanni [1 ]
Buticchi, Giampaolo [1 ]
Liserre, Marco [1 ]
Vournas, Constantine [2 ]
机构
[1] Univ Kiel, Chair Power Elect, D-24143 Kiel, Germany
[2] Natl Tech Univ Athens, Sch Elect & Comp Engn, Athens 15669, Greece
基金
欧洲研究理事会;
关键词
Smart transformer; solid state transformer; load voltage sensitivity; load reduction; overload control; DISTRIBUTION-SYSTEMS; VOLTAGE STABILITY; POWER-FLOW; MODELS;
D O I
10.1109/TSG.2016.2614846
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The higher variability introduced by distributed generation leads to fast changes in the aggregate load composition, and thus in the power response during voltage variations. The smart transformer, a power electronics-based distribution transformer with advanced control functionalities, can exploit the load dependence on voltage for providing services to the distribution and transmission grids. In this paper, two possible applications are proposed: 1) the smart transformer overload control by means of voltage control action and 2) the soft load reduction method, that reduces load consumption avoiding the load disconnection. These services depend on the correct identification of load dependence on voltage, which the smart transformer evaluates in real time based on load measurements. The effect of the distributed generation on net load sensitivity has been derived and demonstrated with the control hardware in loop evaluation by means of a real time digital simulator.
引用
收藏
页码:2606 / 2615
页数:10
相关论文
共 25 条
[1]   Contribution of Distribution Network Control to Voltage Stability: A Case Study [J].
Aristidou, Petros ;
Valverde, Gustavo ;
Van Cutsem, Thierry .
IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (01) :106-116
[2]   Analysis of the frequency-based control of a master/slave micro-grid [J].
Buticchi, Giampaolo ;
De Carne, Giovanni ;
Barater, Davide ;
Zou, Zhixiang ;
Liserre, Marco .
IET RENEWABLE POWER GENERATION, 2016, 10 (10) :1570-1576
[3]  
Cutsem T.V., 1998, Voltage Stability of Electric Power Systems
[4]  
De Carne Giovanni, 2015, 2015 IEEE Power & Energy Society General Meeting, P1, DOI 10.1109/PESGM.2015.7286090
[5]   On-Line Load Sensitivity Identification in LV Distribution Grids [J].
De Carne, Giovanni ;
Liserre, Marco ;
Vournas, Costas .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (02) :1570-1571
[6]  
Delille G, 2015, PROC IEEE EINDHOVEN, V2015, P1, DOI 10.1109/PTC.2015.7232697
[7]  
Dong Z. Y., 2012, C4605 CIGRE WG
[8]   Voltage-Sensitive Load Controllers for Voltage Regulation and Increased Load Factor in Distribution Systems [J].
Douglass, Philip J. ;
Garcia-Valle, Rodrigo ;
Ostergaard, Jacob ;
Tudora, Octavian Constantin .
IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) :2394-2401
[9]   Frequency Control in Isolated/Islanded Microgrids Through Voltage Regulation [J].
Farrokhabadi, Mostafa ;
Canizares, Claudio A. ;
Bhattacharya, Kankar .
IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (03) :1185-1194
[10]   Laboratory measurements and models of modern loads and their effect on voltage stability studies [J].
Hajagos, LM ;
Danai, B .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (02) :584-591