Numerical modeling and fatigue analysis of the dynamic response of main pump cable in nuclear power plant

被引:0
作者
Jingqi, Wang [1 ]
Lixia, Guo [1 ]
Wei, Liu [2 ]
Yadong, Wang [3 ]
Dongfang, Wu [3 ]
Zimeng, Chen [2 ]
机构
[1] Jiangsu Nuclear Power Corporation, LTD, Jiangsu, Lianyungang
[2] China Nuclear Power Operation Technology Corporation LTD, Wuhan
[3] CNNP Operation Maintenance Technology Corporation LTD, Hangzhou
关键词
cyclic loading; fatigue life; finite element analysis; the main pump cable; thermal-structure coupling;
D O I
10.2478/amns-2024-1848
中图分类号
学科分类号
摘要
The structural temperature rise and thermal stress caused by operation current and ambient temperature are some of the main factors affecting cable fatigue life. Combined with the operating and environmental conditions of the main cooling pump of the nuclear power plant, the thermal-structural coupling field numerical modeling and fatigue analysis of the 6kV single-core and three-core cable of the main pump is carried out. Based on obtaining the steady-state operating current, the motor start-up transient current, and the circulating ambient temperature, the thermal-structural coupling field numerical model of the main pump cable is established using the load transfer method to obtain the thermal and stress field distribution of the internal structural layer. The load history of one cycle is extracted for the fatigue numerical simulation of the main pump cable. The stress time history of the cable structure layer was constructed by the stress calculation results and the load time history of a single period, and the fatigue life of the main pump cable was obtained based on the S-N curve of the main insulation material and the Miner's linear cumulative damage theory. The simulation results show that the force acting on the main pump cable by the operating current and ambient temperature is an approximately symmetric cyclic load of constant amplitude. The life cycle of the cable can reach 2.235∗e4 times, and the overall life of the cable is about 63.97 years. This study can provide theoretical guidance for the safety and reliability design and state operation and maintenance of the main pump cable of the nuclear power plant. © 2024 Wang Jingqi et al., published by Sciendo.
引用
收藏
相关论文
共 50 条
  • [21] Vortex-Induced Vibration and Fatigue Characteristics Analysis of Submarine Power Cable Based on Model Similarity Theory
    Lv, Anqiang
    Zhou, Zixuan
    Huang, Youcong
    Zheng, Zhongnan
    Lin, Ziqi
    Zhang, Ying
    IEEE ACCESS, 2024, 12 : 103251 - 103259
  • [22] Numerical Modeling of the Quasi-static and Dynamic Response of an Earthen Dam: Case of the Ourkiss Dam
    Baghzim, Hassiba
    Karech, Toufik
    Sekhri, Abdelhak
    INDIAN GEOTECHNICAL JOURNAL, 2024, 55 (2) : 766 - 780
  • [23] Experimental and numerical investigation on the seismic behavior of above ground high density polyethylene pipe in nuclear power plant
    Shi, Jianfeng
    Ge, Zhoutian
    Cao, Yuhua
    Gao, Jianyong
    Yu, Fa
    Yao, Riwu
    STRUCTURES, 2024, 59
  • [24] Analysis on damage evolution and corrosion fatigue performance of high-strength steel wire for bridge cable: Experiments and numerical simulation
    Wang, Y.
    Zheng, Y. Q.
    Zhang, W. H.
    Lu, Q. R.
    THEORETICAL AND APPLIED FRACTURE MECHANICS, 2020, 107
  • [25] Study on Transient Response Analysis and Fatigue Life Evaluation of Water Pump Volute Casing under Impact Load
    Li, Min
    Yin, Zenghui
    Shi, Kui
    Liu, Jianxin
    Du, Huiyong
    MECHANICAL ENGINEERING AND GREEN MANUFACTURING II, PTS 1 AND 2, 2012, 155-156 : 550 - 554
  • [26] SICODYN international benchmark on dynamic analysis of structure assemblies: variability and numerical-experimental correlation on an industrial pump
    Audebert, Sylvie
    MECANIQUE & INDUSTRIES, 2010, 11 (06): : 439 - 451
  • [27] Analysis of vibration response of containment foundation in nuclear power station after munitions bombing
    Shen Zu-wu
    Liu Guo-qiang
    Wang Tian-yun
    Liu Shui-jiang
    ROCK AND SOIL MECHANICS, 2009, 30 (08) : 2540 - 2544
  • [28] An overview of engineering numerical methods for the dynamic analysis of a nuclear reactor with fluid-structure interaction modelling
    Sigrist, Jean-Francois
    INTERNATIONAL JOURNAL OF MULTIPHYSICS, 2009, 3 (01) : 31 - 60
  • [29] SICODYN international benchmark on dynamic analysis of structure assemblies: variability and numerical-experimental correlation on an industrial pump (part 2)
    Audebert, Sylvie
    Mikchevitch, Alexei
    Zentner, Irmela
    MECHANICS & INDUSTRY, 2014, 15 (01) : 1 - 17
  • [30] Seismic finite element analysis of passive rectangular heat pipe heat exchange tank in nuclear power plant
    He, Jiadong
    Lu, Song
    Kang, Jian
    Lu, Tao
    NUCLEAR ENGINEERING AND DESIGN, 2025, 432