Single-phase Grounding Fault Detection in Non-solidly Earthed Network Based on Negative Sequence Characteristics of Low-voltage Side

被引:0
作者
Zhang M. [1 ,4 ]
Luan W. [2 ]
Ai X. [1 ]
Xu B. [3 ]
机构
[1] School of Electrical and Electronic Engineering, North China Electric Power University, Changping District, Beijing
[2] School of Electrical and Information Engineering, Tianjin University, Nankai District, Tianjin
[3] School of Electrical and Electronic Engineering, Shandong University of Technology, Shandong Province, Zibo
[4] China Electric Power Research Institute, Haidian District, Beijing
来源
Dianwang Jishu/Power System Technology | 2024年 / 48卷 / 04期
关键词
fault detection; low-voltage measurements; negative sequence signals; single-phase grounding fault; un-effectual grounding system;
D O I
10.13335/j.1000-3673.pst.2023.1698
中图分类号
学科分类号
摘要
With the gradual maturity of intelligent terminal measurement technology in the low-voltage distribution network, achieving holographic perception on the low-voltage side while also possessing the ability to monitor multiple points of the medium-voltage distribution network. This paper proposed a method of single-phase grounding fault detection for an un-effectual grounding system based on the low-voltage side's negative-sequence characteristics. The characteristics of the negative sequence signal at the low-voltage side after a single-phase grounding fault occurred on the medium-voltage side are analyzed; the negative-sequence current can distinguish the fault and non-fault lines. after setting the ratio coefficient of negative-sequence voltage and positive-sequence voltage, multi-point collaborative calculation and comparison can be used to determine the section of the fault point. The unbalanced load at the low-voltage side and the special case of a fault point at one end of the line are considered. Through the simulation of medium-voltage and low-voltage combined distribution systems in MATLAB software and dynamic model experiment, it is verified that the proposed method has good robustness and accuracy. Monitoring the status information of the medium-voltage distribution network through the smart distribution transformer terminal to realize the fault detection of neutral un-effectual grounding systems has great potential in practical application and implementation. © 2024 Power System Technology Press. All rights reserved.
引用
收藏
页码:1654 / 1662
页数:8
相关论文
共 23 条
[1]  
CHENG Lu, CHEN Qiaofu, A survey on faulty line selection technology for single-phase grounded transmission line in small current neutral grounded system[J], Power System Technology, 33, 18, pp. 219-224, (2009)
[2]  
ZHANG Mingze, LUAN Wenpeng, AI Xin, Single-phase grounding fault detection in non-solidly earthed network based on low-voltage measurements[J], Power System Technology, 47, 8, pp. 3457-3466, (2023)
[3]  
LIANG Dong, XU Bingyin, TANG Yi, Model and detection method for tree-contact single-phase-to-ground faults on 10kV overhead lines[J], Proceedings of the CSEE, 41, 15, pp. 5221-5232, (2021)
[4]  
LIU Shuo, LIU Hao, BI Tianshu, Fault detection of distribution network considering high impedance faults[J], Power System Technology, 47, 8, pp. 3438-3447, (2023)
[5]  
QIN Jike, NING Xin, FAN Songhai, Discharge ignition mechanism of tree-contacting single-phase-to-ground faults of overhead lines[J], Power System Technology, 47, 3, pp. 1289-1298, (2023)
[6]  
REN Wei, XUE Yongduan, YANG Fan, Modeling and analysis of arc grounding faults in isolated neutral distribution network[J], Power System Technology, 45, 2, pp. 705-712, (2021)
[7]  
Jian LIU, ZHANG Xiaoqing, SHEN Wei, Performance testing of single phase to earth fault location for distribution network with neutral point non-effectively grounded systems[J], Automation of Electric Power Systems, 42, 1, pp. 138-143, (2018)
[8]  
ZENG Xiangjun, YIN Xainggen, YU Yongyuan, New methods for control and protection relay in a compensated medium voltage distribution network based on injecting various frequency current[J], Proceedings of the CSEE, 20, 1, pp. 29-32, (2000)
[9]  
LUAN Xiaoming, WU Shouyuan, JIA Chunjuan, Fault line selection principle of single-phase-to-ground fault based on improved zero-sequence admittance[J], Power System Technology, 46, 1, pp. 353-360, (2022)
[10]  
SANG Zaizhong, ZHANG Huifen, PAN Zhencun, Protection for single phase to earth fault line selection for ungrounded power system by injecting signal[J], Automation of Electric Power Systems, 20, 2, pp. 11-12, (1996)