Optimization of Triple Effect Vapor Absorption Refrigeration System: A Statistical Approach

被引:0
作者
Naga, Sakshi [1 ]
Rajput, S. P. S. [1 ]
机构
[1] Maulana Azad Natl Inst Technol, Dept Mech Engn, Bhopal 462003, Madhya Pradesh, India
来源
JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME | 2024年 / 146卷 / 10期
关键词
triple-effect; vapor absorption refrigeration system; COP; ECOP; optimization; statistical techniques; alternative energy sources; energy conversion/systems; energy systems analysis; EXERGY ANALYSIS; PERFORMANCE; ENERGY; SINGLE; HEAT; CYCLE;
D O I
10.1115/1.4065654
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The present paper optimized the first and second law performance of the triple-effect vapor absorption refrigeration systems (TE-VARS) using statistical techniques like Taguchi, Taguchi-based gray relational analysis (GRA), and response surface methodology (RSM)-based GRA methods, which provide the most accurate and optimized results. Liquified petroleum gas (LPG) and compressed natural gas (CNG) are considered as the source of energy to operate TE-VARS, as the system requires significantly higher generator temperature. Also, volume flowrate of these gases along with the annual operating cost to drive the system have been presented. A thermodynamic model was first formulated using engineering equation solver ( EES ) software for the computation of the coefficient of performance (COP) and exergetic efficiency (ECOP). The most influential parameters like temperature in the main generator, concentration, and pressure at different components are studied and determined using analysis of variance (ANOVA) and Taguchi methods. The optimum parameters were determined based on the mean effect plot of S/N ratios for COP and ECOP. It has been found that the maximum COP and ECOP were calculated to be 1.915 and 0.15, respectively, under the Taguchi method. Furthermore, Taguchi-GRA was used for the simultaneous optimization of the operating parameters and performance of the system. It is observed that the absorber temperature is the most influential parameter for affecting COP and ECOP. Moreover, a RSM-based GRA method was also applied and developed regression models that yield most optimum COP and ECOP as 1.963 and 0.1606, respectively. Comparison shows that the RSM-based GRA method provides the most optimum conditions, which is one of the key finding of the present study. Also, rate of exergy destruction at each component of TE-VARS has been plotted under optimized operating conditions. The optimum volume flowrate for LPG and CNG comes out to be 0.057 and 0.177 m(3)/s, while the minimum operating cost (yearly) are 299.827$ and 183.293$, respectively.
引用
收藏
页数:13
相关论文
共 50 条
  • [21] Thermoeconomic and feasibility analysis of novel transcritical vapor compression-absorption integrated refrigeration system
    Jain, Vaibhav
    Colorado, D.
    ENERGY CONVERSION AND MANAGEMENT, 2020, 224
  • [22] Optimization of a multistage vapor-compression refrigeration system for various refrigerants
    Baakeem, Saleh S.
    Orfi, Jamel
    Alabdulkarem, Abdullah
    APPLIED THERMAL ENGINEERING, 2018, 136 : 84 - 96
  • [23] Experimental investigation of a vapor absorption refrigeration system
    Horuz, I
    Callander, TMS
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (01): : 10 - 16
  • [24] Optimization of geothermal energy aided absorption refrigeration system-GAARS: A novel ANN-based approach
    Tugcu, Abtullah
    Arslan, Oguz
    GEOTHERMICS, 2017, 65 : 210 - 221
  • [25] Three-objective optimization of a novel triple-effect absorption heat transformer combined with a water desalination system
    Mahmoudi, S. M. S.
    Salehi, S.
    Yari, M.
    ENERGY CONVERSION AND MANAGEMENT, 2017, 138 : 131 - 147
  • [26] Thermodynamic analysis and optimization of variable effect absorption refrigeration system using multi-island genetic algorithm
    Zhang, Ke
    Ma, Haijing
    Li, Qingyang
    Wang, Dechang
    Song, Qinglu
    Wang, Xiaohe
    Kong, Xiangqiang
    ENERGY REPORTS, 2022, 8 : 5443 - 5454
  • [27] Thermodynamic optimization and chemical exergy quantification for absorption-based refrigeration system
    Gupta, A.
    Anand, Y.
    Anand, S.
    Tyagi, S. K.
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2015, 122 (02) : 893 - 905
  • [28] Optimization and comprehensive exergy-based analyses of a parallel flow double-effect water-lithium bromide absorption refrigeration system
    Bagheri, B. Safarnezhad
    Shirmohammadi, R.
    Mahmoudi, S. M. S.
    Rosen, M. A.
    APPLIED THERMAL ENGINEERING, 2019, 152 : 643 - 653
  • [29] Performance assessment of a solar based novel combined cycle using vapor compression-absorption refrigeration system for trigeneration application
    Khan, Yunis
    Singh, Pawan Kumar
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART C-JOURNAL OF MECHANICAL ENGINEERING SCIENCE, 2025,
  • [30] Energy and exergy evaluation of triple-effect H2O/LiBr absorption cooling system
    Solanki, Alka
    Pal, Yash
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2020, 43 (01) : 3626 - 3637