摘要
This paper proposed a new transformer protection scheme based on phase space trajectory recognition and multi-criteria fusion. Firstly, the basic concept of phase space and the method of selecting phase space parameters were given. Then, the phase space trajectory formed by fault component of instantaneous power (FCIP) was analyzed under different conditions such as internal faults, external faults and switching on the unloaded transformer. Given such analyses, a new criterion for transformer protection based on phase space trajectory identification was proposed. Furthermore, two new protection criteria were designed and all criteria were skillfully integrated based on the change rule of voltage and current under exceptional circumstances such as CT saturation, switching on the unloaded transformer with high resistance faults and short-term transferring faults. Finally, a new transformer protection scheme was designed. The simulation results based on PSCAD/EMTDC verify the effectiveness and superiority of the new scheme. © 2020 Chin. Soc. for Elec. Eng.
引用
收藏
页码:1924 / 1937
页数:13
相关论文
共 24 条
  • [1] Deng M., Yao D., Ni C., Et al., Inrush current recognition in power transformer based on electronic transformer, Power System Protection and Control, 41, 18, pp. 149-153, (2013)
  • [2] Wang W., Consideration on the improper operation of transformer protection, Electric Power Automation Equipment, 21, 10, pp. 1-3, (2001)
  • [3] Zheng T., Liu W., Xiao S., Et al., A new algorithm based on the mathematical morphology for power transformer protection, Proceedings of the CSEE, 24, 7, pp. 18-24, (2004)
  • [4] Bi D., Zhang X., Yang H., Et al., Correlation analysis of waveforms in non-saturation zone based method to identify magnetizing inrush in transformer, Automation of Electric Power Systems, 30, 6, (2006)
  • [5] Wang Z., Xu Y., Wang X., Et al., Study on the novel transformer protection principle based on the transformer model, Proceedings of the CSEE, 23, 12, pp. 54-58, (2003)
  • [6] Hao Z., Zhang B., Chu Y., Et al., Study on transformer protection principle based on equivalent circuit equilibrium equation, Proceedings of the CSEE, 26, 10, pp. 67-72, (2006)
  • [7] Lin X., Liu P., Gao Y., A novel method to identify the saturation of the current transformer using mathematical morphology, Proceedings of the CSEE, 25, 5, pp. 44-48, (2005)
  • [8] Cao Y., Li Y., Zhang X., Et al., A new on-line criterion for current transformer saturation based on wavelet transform, Automation of Electric Power Systems, 25, 10, pp. 27-30, (2001)
  • [9] Zhang Q., Zhao X., Tan J., Multiple derivatives based CT Saturation detection method, Relay, 36, 5, pp. 10-13, (2008)
  • [10] Zhao Y., Lu Y., An asynchronous method based saturation criterion for CT in busbar protection, Power System Technology, 30, 5, pp. 86-90, (2006)