Summertime performance of an automated lighting and blinds control system

被引:48
作者
Roche, L. [1 ]
机构
[1] BRE, Bucknalls Lane, Garston, Herts WD25 9XX, United Kingdom
来源
Lighting Research and Technology | 2002年 / 34卷 / 01期
关键词
Control systems - Energy efficiency - Opacity - Sensors - Solar radiation;
D O I
10.1191/1365782802li026oa
中图分类号
学科分类号
摘要
An innovative automated blind and lighting control system was developed to eliminate direct solar penetration and keep working plane illuminances within an optimal range, while making maximum use of daylight, and minimizing blind movement. Data collected from a controlled experiment indicate that the system eliminated direct solar glare and kept the working plane illuminance within the target range, while providing only 30% more electric lighting than a theoretical system with no blinds and perfect knowledge of the working plane illuminance. The system needed to provide 60% less electric lighting than a similar system with switchable rather than dimmable luminaires. Total blind movement varied from less than 1 min to over 6 min in one day depending on the weather, with an average of 190 s. Similar integrated systems have the potential to save a large fraction of the electricity used for lighting, while providing an amenable visual environment.
引用
收藏
页码:11 / 27
相关论文
empty
未找到相关数据