Scheme study on simultaneous AC-DC distribution network

被引:0
|
作者
Xu X. [1 ]
Tai N. [1 ]
Fan C. [1 ]
Zheng X. [1 ]
机构
[1] Key Laboratory of Control of Power Transmission and Conversion, School of Electronic Information and Electrical Engineering, Shanghai Jiao Tong University, Minhang District, Shanghai
来源
基金
中国国家自然科学基金;
关键词
DC load; Distributed generation; Economy; MV distribution network; Simultaneous AC-DC; Zigzag transformer;
D O I
10.13335/j.1000-3673.pst.2016.07.028
中图分类号
学科分类号
摘要
Aiming at new problems occurring in power system and special structure of distribution network with multiple feeders, this paper puts forward simultaneous AC-DC system scheme based on zigzag transformer and designs AC-DC distribution network topology. Under premise of not changing original AC line insulation and structure, AC-DC superposition method is analyzed, maximum power transmitted is calculated and feasibility of the scheme is verified with simulation in this paper. Considering different proportions of AC and DC component of power source and load, economy between AC-DC and traditional AC power distribution system is analyzed comparatively. Simulation results show feasibility of distribution scheme in MV distribution network with zigzag transformer. Calculation example shows that the scheme could improve transmission capacity of distribution lines and alleviate tense situation of power supply and distribution. Economic analysis provides basis for choosing distribution mode for distribution network with AC-DC source and load. The scheme provides a new solution for distributed generation and continuously increasing DC load access to distribution network. © 2016, Power System Technology Press. All right reserved.
引用
收藏
页码:2120 / 2127
页数:7
相关论文
共 25 条
  • [11] Basu K.P., Stability enhancement of power system by controlling HVDC power flow through the same AC transmission line, IEEE Symposium on Industrial Electronics & Applications, ISIEA 2009, pp. 663-668, (2009)
  • [12] Andreotti A., Lauria D., Mottola F., Optimal design of combined AC-DC transmission lines, Power Electronics Electrical Drives Automation and Motion. SPEEDAM 2008, pp. 411-415, (2008)
  • [13] Yong J., Xu X., Zeng L., Et al., Overview of low voltage DC power supply system, Proceedings of the CSEE, 33, 7, pp. 42-52, (2013)
  • [14] Liang Y., Hu Z., Chen Y., A survey of distribution generation and its application in power system, Power System Technology, 27, 12, pp. 71-76, (2003)
  • [15] Zhou P., Guo Z., Modeling and application of Zig-zag transformer, Electric Power Automation Equipment, 27, 12, pp. 93-95, (2007)
  • [16] Zhang L., Liu M., Zhao T., Et al., Application of intelligent inductive filtering in single wire AC and DC power distribution, Power System Technology, 39, 8, pp. 2371-2376, (2015)
  • [17] Ke G., Yi L., Zhou S., Et al., Study on the capacity improvement of transmission line based on double circuit AC-DC system, Power System Protection and Control, 41, 6, pp. 25-31, (2013)
  • [18] Bo H., Yi L., Dong P., Et al., Simulation Research of interface transformer of new AC-DC hybrid power supply system based on Ansoft and solving the problem of magnetic saturation caused by DC, Journal of Power Supply, 11, 5, pp. 69-74, (2013)
  • [19] Chen Y., Tang Y., Test and analysis on the large impact current of lightning protection and lightning arrester combination in distribution transformer, Journal of Shanghai Jiao Tong University, 13, 4, pp. 157-167, (1979)
  • [20] Wang S., Tan L., Li Y., Et al., Control strategy for the unbalanced load control of chain star STATCOM, Proceedings of the CSEE, 33, 27, pp. 20-27, (2013)