Single ended fault location algorithm based on detection of initial reverse polarity traveling wave

被引:0
|
作者
机构
[1] School of Electrical Engineering, Shandong University
[2] Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education, Shandong University
[3] Liaocheng Electric Power Corporation
[4] Binzhou Electric Power Corporation
来源
Liang, J. | 1600年 / Automation of Electric Power Systems Press卷 / 37期
关键词
Fault location; Initial reverse polarity traveling wave; Single ended; Traveling wave;
D O I
10.7500/AEPS201107228
中图分类号
学科分类号
摘要
A novel single ended fault location algorithm based on the initial reverse polarity traveling wave (RPTW) detection is proposed. Research shows that the RPTW has less influencing factors, which ensures the high detection reliability, moreover, the time when the RPTW arrives has a certain relationship with fault location, has a piecewise linear characteristic. According to the characteristics of RPTW and combining the initial traveling wave, the fault section and the primary fault location can be determined as soon as the initial RPTW can be identified. After that the exact fault point will be located using other fault information contained in the single ended traveling waves. Only the initial traveling wave and initial PRTW have been used in the present algorithm, which will guarantee the detection accuracy. Simulation results show that the proposed algorithm can effectively locate the fault point, and obviously improve the single ended fault location's reliability and accuracy. © 2013 State Grid Electric Power Research Institute Press.
引用
收藏
页码:108 / 113
页数:5
相关论文
共 12 条
  • [11] (1996)
  • [12] Dong X., Geng Z., Ge Y., Et al., The application of wavelet transform to power system fault signal analysis, Proceedings of the CSEE, 17, 6, pp. 421-424, (1997)