A robust current control strategy for grid-connected inverters with LCL filters

被引:0
|
作者
Xu, Jinming [1 ]
Xie, Shaojun [1 ]
Huang, Ruhai [1 ]
机构
[1] College of Automation Engineering, Nanjing University of Aeronautics and Astronautics
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2012年 / 36卷 / 19期
关键词
Active damping; Current control; Filters; Grid-connected inverters; Robustness;
D O I
10.3969/j.issn.1000-1026.2012.19.018
中图分类号
学科分类号
摘要
For grid-connected inverters, the switching frequency harmonics can be effectively attenuated through LCL filters, however, the grid current is easy to be resonated, which results in the difficulty in the system design. If the weighted average of the currents through two inductors is used for the feedback control, the high order control of LCL system is degraded to a low order one. In this way it is easy to obtain good system performance. However, there are still under-damped conjugate poles depending on the non-ideal factors in the grid current. The inhibitions of harmonics at the resonance frequencies are poor and the system bandwidth is limited. An idea of combining active damping and weighted current control together is proposed to overcome these difficulties. Besides, the control characteristics of the proposed method, including the robustness, are investigated and compared with those of the weighted current control with passive damping. The proposed control strategy can realize better robustness and further improve the system performance through a simple design procedure. © 2012 State Grid Electric Power Research Institute Press.
引用
收藏
页码:99 / 104
页数:5
相关论文
共 17 条
  • [11] Malinowski M., Bernet S., A simple voltage sensorless active damping scheme for three-phase PWM converters with an LCL filter, IEEE Trans on Industrial Electronics, 55, 4, pp. 1876-1880, (2008)
  • [12] Wang X., Ruan X., Liu S., Control strategy for grid-connected inverter to suppress current distortion effected by background harmonics in grid voltag, Proceedings of the CSEE, 31, 6, pp. 7-14, (2011)
  • [13] Huang Y., Jiang X., Qiu A., A novel active damping control scheme for a three-phase active rectifier with LCL-filter, Transactions of China Electrotechnical Society, 23, 9, pp. 86-91, (2008)
  • [14] Dannehl J., Fuchs F.W., Hansen S., Et al., PI state space current control of grid-connected PWM converters with LCL filters, IEEE Trans on Power Electronics, 25, 9, pp. 2320-2330, (2010)
  • [15] Yang S., Zhang X., Zhang C., Et al., Strategy design of multiple feedback loop control for grid-connected voltage source inverter with LCL filter, Automation of Electric Power Systems, 35, 5, pp. 66-70, (2011)
  • [16] Shen G., Xu D., Current control for grid-connected inverters by splitting the capacitor of LCL filter, Proceedings of the CSEE, 28, 18, pp. 36-41, (2008)
  • [17] Shen G., Zhu X., Zhang J., Et al., A new feedback method for PR current control of LCL-filter-based grid-connected inverter, IEEE Trans on Industrial Electronics, 57, 6, pp. 2033-2041, (2010)