A robust current control strategy for grid-connected inverters with LCL filters

被引:0
|
作者
Xu, Jinming [1 ]
Xie, Shaojun [1 ]
Huang, Ruhai [1 ]
机构
[1] College of Automation Engineering, Nanjing University of Aeronautics and Astronautics
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2012年 / 36卷 / 19期
关键词
Active damping; Current control; Filters; Grid-connected inverters; Robustness;
D O I
10.3969/j.issn.1000-1026.2012.19.018
中图分类号
学科分类号
摘要
For grid-connected inverters, the switching frequency harmonics can be effectively attenuated through LCL filters, however, the grid current is easy to be resonated, which results in the difficulty in the system design. If the weighted average of the currents through two inductors is used for the feedback control, the high order control of LCL system is degraded to a low order one. In this way it is easy to obtain good system performance. However, there are still under-damped conjugate poles depending on the non-ideal factors in the grid current. The inhibitions of harmonics at the resonance frequencies are poor and the system bandwidth is limited. An idea of combining active damping and weighted current control together is proposed to overcome these difficulties. Besides, the control characteristics of the proposed method, including the robustness, are investigated and compared with those of the weighted current control with passive damping. The proposed control strategy can realize better robustness and further improve the system performance through a simple design procedure. © 2012 State Grid Electric Power Research Institute Press.
引用
收藏
页码:99 / 104
页数:5
相关论文
共 17 条
  • [1] Liserre M., Blaabjerg F., Hansen S., Design and control of an LCL-filter based active rectifier, IEEE Trans on Industry Applications, 41, 2, pp. 1281-1291, (2005)
  • [2] Wang S., Lu Z., A harmonics suppression method for lithium battery grid integration system, Automation of Electric Power Systems, 33, 19, pp. 90-95, (2009)
  • [3] Liserre M., Teodorescu R., Blaabjerg F., Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values, IEEE Trans on Power Electronics, 21, 1, pp. 263-272, (2006)
  • [4] Dannehl J., Wessels C., Fuchs F.W., Limitations of voltage-oriented PI current control of grid-connected PWM rectifiers with LCL filters, IEEE Trans on Industrial Electronics, 56, 2, pp. 380-388, (2009)
  • [5] Xu J., Xie S., Xiao H., Research on control mechanism of active damping for LCL filters, Proceedings of the CSEE, 32, 9, pp. 27-33, (2012)
  • [6] Twining E., Holmes D.G., Grid current regulation of a three-phase voltage source inverter with an LCL input filter, IEEE Trans on Power Electronics, 18, 3, pp. 888-895, (2003)
  • [7] Xu Z., Xu A., Xie S., Dual-loop grid current control technique for grid-connected inverter using an LCL filter, Proceedings of the CSEE, 29, 27, pp. 36-41, (2009)
  • [8] Liu F., Duan S., Zha X., Design of two loop controller in grid-connected inverter with LCL filter, Proceedings of the CSEE, 29, SUPPL.1, pp. 234-240, (2009)
  • [9] Dannehl J., Fuchs F.W., Hansen S., Et al., Investigation of active damping approaches for PI-based current control of grid-connected PWM converters with LCL filters, IEEE Trans on Industry Applications, 46, 4, pp. 1509-1517, (2010)
  • [10] Yu T., Choi S., Kim H., Indirect current control algorithm for utility interactive inverters for seamless transfer, Proceedings of the 37th Power Electronics Specialists Conference, pp. 1-6