Experiments for actual performance evaluation of room air-conditioners in an experimental house: Research on performance evaluation of room air-conditioners part 1

被引:0
作者
Sumiyoshi, Daisuke [1 ]
Ogino, Takashi [2 ]
Miura, Hisashi [3 ]
Hosoi, Akinori [4 ]
Sawachi, Takao [5 ]
机构
[1] Faculty of Human Environment Studies, Kyushu University
[2] Department of Environmental Engineering, Building Research Institute
来源
Journal of Environmental Engineering (Japan) | 2013年 / 78卷 / 688期
关键词
Actual performance; COP; Evaluation approach; JIS experiment; Room air-conditioner;
D O I
10.3130/aije.78.497
中图分类号
学科分类号
摘要
In this research, the experiments to measure the actual performance of room air-conditioners were performed to make appropriate evaluation method of them. Results are as follows: 1. Partial load rates of air-conditioners are very low: especially in the heating use there was a machine whose partial load rates are less than 10 % in 95% of the entire operating hours. 2. COP in actual usage situation was lower than JIS experiment result in most of machines. This tendency was conspicuously appeared in heating. 3. The evaluation approach that can evaluate the actual performance at the heating period and at the low partial load appropriately should be considered.
引用
收藏
页码:497 / 505
页数:8