Modelling of heat and mass transfer in a two-phase closed thermosyphon

被引:1
|
作者
Lataoui, Zied [1 ]
Benselama, Adel M. [2 ]
机构
[1] Univ Monastir, Ecole Natl Ingenieurs Monastir, Lab Etud Syst Therm & Energet, Ave Ibn El Jazzar, Monastir 5019, Tunisia
[2] Univ Poitiers, CNRS ENSMA, Inst Pprime FTC COST, 1 Ave Clement Ader, F-86961 Futuroscope, France
关键词
Thermosyphon; Two-phase flow; Volume of fluid; Phase change; Heat transfer performance; INCLINATION ANGLE; FILL RATIO; THERMAL PERFORMANCE; SOLAR COLLECTORS; PIPE; WATER; CONDENSATION; SIMULATION; PARAMETERS;
D O I
10.1016/j.energy.2024.133851
中图分类号
O414.1 [热力学];
学科分类号
摘要
A CFD model is developed to simulate the heat and mass transfer inside a two-phase closed thermosyphon. Based on the "volume of fluid" method, governing equations are solved using the OpenFOAM utilities. The involved complex phenomena like evaporation and condensation occurring in such a device and associated with twophase flow are investigated. A noticeable novelty of this model is that neither artificial, ad hoc nor specific nucleation means is needed to trigger evaporation along the heat source walls; an altogether unique phase change model is valid and uniformly used within the flow occurring inside the thermosyphon. The numerical results are compared to well-documented experimental data showing very good agreement: maximum deviation of 1 % and 2.7 % are obtained for mean temperature and condenser pressure, respectively. The axial thermal resistance values are also compared with the experimental data. Fair agreement was obtained in the overall equivalent resistance (26.4-32.5 %) and in the evaporator axial resistance (25-27.5 %). In addition, the evaporator slug flow pattern is successfully captured by the model. The liquid fraction distribution inside the thermosyphon is analyzed as time evolves. It shows, in particular, that bubble activation and growth have the same trend as previous experimental visualization results, namely denser activation close to the meniscus. The velocity distribution shows also recirculation in the top of the condenser zones and above the liquid meniscus in the evaporator zone, too, as a direct effect of buoyancy and natural convection. As activated bubbles rise and coalesce into larger bubbles, the occurrence of a slug flow is observed. Furthermore, the tested model had shown its efficiency to predict the main fluid flow and thermal characteristics of a thermosyphon when pseudo-steady state is reached.
引用
收藏
页数:16
相关论文
共 50 条
  • [31] Experimental Investigation on Heat Transfer in Two-Phase Closed Thermosyphon Containing Non-Condensable Gas
    Song, Binglin
    Meng, Guoying
    Huang, Wei
    Wang, Aiming
    Cheng, Xiaohan
    Yang, Jie
    ENERGIES, 2024, 17 (18)
  • [32] Critical heat flux of a two-phase closed thermosyphon with fins
    Wasan Pinate
    Sampan Rittidech
    Pattanapol meena
    Journal of Mechanical Science and Technology, 2018, 32 : 2357 - 2364
  • [33] Critical heat flux of a two-phase closed thermosyphon with fins
    Pinate, Wasan
    Rittidech, Sampan
    Meena, Pattanapol
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2018, 32 (05) : 2357 - 2364
  • [34] An experimental investigation on the evaporation and condensation heat transfer of two-phase closed thermosyphons
    Jafari, Davoud
    Di Marco, Paolo
    Filippeschi, Sauro
    Franco, Alessandro
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2017, 88 : 111 - 123
  • [35] Thermal performance of a two-phase closed thermosyphon for waste heat recovery system
    Kannan M.
    Natarajan E.
    Journal of Applied Sciences, 2010, 10 (05) : 413 - 418
  • [36] Experimental investigation of a stainless steel two-phase closed thermosyphon
    Lataoui, Zied
    Jemni, Abdelmajid
    APPLIED THERMAL ENGINEERING, 2017, 121 : 721 - 727
  • [37] Thermal performance enhancement in two-phase closed thermosyphon with sandblasted evaporator surface
    Kang, Sukkyung
    Lee, Seokjin
    Lee, Jungho
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2024, 159
  • [38] Influence of system pressure on the boiling heat transfer coefficient in a closed two-phase thermosyphon loop
    Khodabandeh, R
    Palm, B
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2002, 41 (07) : 619 - 624
  • [39] Heat transfer characteristics of a two-phase closed thermosyphon considering the working fluid filling ratio
    Oh, S. H.
    Kim, S. I.
    Choi, J. W.
    Lee, K. J.
    Chun, W. P.
    HEAT TRANSFER XIV: SIMULATION AND EXPERIMENTS IN HEAT TRANSFER AND ITS APPLICATIONS, 2016, 106 : 87 - 93
  • [40] The rectangular two-phase closed thermosyphon: A case study of two-phase internal flow patterns behaviour for heat performance
    Chompookham, Teerapat
    Sichamnan, Surachet
    Bhuwakietkumjohn, Nipon
    Parametthanuwat, Thanya