Effect of integrated large capacity synchronous condenser on reactive power and voltage sensitivity for AC/DC power system

被引:0
|
作者
Huang H. [1 ,2 ,3 ]
Pan X. [4 ]
Li L. [4 ]
Yang L. [1 ,2 ,3 ]
Lu J. [1 ,2 ,3 ]
Yan J. [4 ]
机构
[1] NARI Group Corporation(State Grid Electric Power Research Institute), Nanjing
[2] NARI Technology Co., Ltd., Nanjing
[3] State Key Laboratory of Smart Grid Protection and Control, Nanjing
[4] College of Energy and Electrical Engineering, Hohai University, Nanjing
来源
| 2018年 / Electric Power Automation Equipment Press卷 / 38期
关键词
AC/DC power system; Fixed capacitor; PQ node; PV node; Reactive power and voltage sensitivity; Synchronous condenser;
D O I
10.16081/j.issn.1006-6047.2018.12.024
中图分类号
学科分类号
摘要
The reactive power and voltage sensitivity of AC/DC power system is an important index to measure the interaction between AC subsystem and DC subsystem, and guide reactive power optimization and control. The gradual application of new generation large capacity SC(Synchronous Condenser) in sending and receiving ends of UHVDC(Ultra High Voltage Direct Current) power system has brought challenges to the existing calculation method of reactive power and voltage sensitivity. Therefore, a sensitivity calculation method for different types of nodes is proposed based on the linearized power flow equation of AC/DC power system, and the physical meaning of the sensitivity concerning PV node is analyzed. The EPRI 36-bus system is taken as an example, and the simulative results verifies the correctness of the proposed method. © 2018, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:162 / 167
页数:5
相关论文
共 18 条
  • [1] Liu Z., Innovation of UHVAC transmission technology in China, Power System Technology, 37, 3, pp. 1-8, (2013)
  • [2] Zhou H., Zhong Y., Applicable occasions of UHVAC/UHVDC transmission and their technology comparisons in China, Electric Power Automation Equipment, 37, 3, (2013)
  • [3] Zheng C., Ma S., Shen X., Et al., Definition, connotation and form of strong HVDC and weak AC and countermeasures for stable operation of hybrid power grid, Power System Technology, 41, 8, pp. 2491-2498, (2017)
  • [4] Wu P., Xu S., Zhao B., Et al., Research of weak sending-end coupling characteristics for bundled wind-thermal power transmission of UHVDC project, Electric Power Automation Equipment, 36, 1, pp. 60-66, (2016)
  • [5] Peschon J., Piercy D.S., Tinney W.F., Et al., Sensitivity in power systems, IEEE Trans on Power Apparatus and Systems, PAS-87, 8, pp. 1687-1696, (1968)
  • [6] Chang Y.C., Liu C.C., Yang W.T., Real-time line flow calculation using a new sensitivity method, Electric Power System Research, 62, 24, pp. 127-133, (1992)
  • [7] Duan X., Yuan J., He Y., Et al., Sensitivity Analysis methods on voltage stability of electric power systems, Automation of Electric Power Systems, 21, 4, pp. 9-12, (1997)
  • [8] Yuan J., Duan X., He Y., Et al., Summarization of the sensitivity analysis method of voltage stability of electric power systems, Power System Technology, 21, 9, pp. 7-10, (1997)
  • [9] Begovic M.M., Control of voltage stability using sensitivity analysis, IEEE Trans on Power Systems, 7, 1, pp. 114-123, (1992)
  • [10] Chen Y.L., Weak bus oriented reactive power planning for system security, IEE Proceedings-Generation, Transmission and Distribution, 143, 6, pp. 541-545, (1996)