Indoor environmental quality assessment in passively ventilated classrooms in Germany and estimation of ventilation energy losses

被引:4
作者
Nehr, Sascha [1 ,2 ,4 ]
Baus, Lukas [1 ,2 ]
Cinar, Hasan [2 ]
Elsen, Ingo [3 ]
Frauenrath, Tobias [3 ]
机构
[1] CBS Int Business Sch, D-50996 Cologne, Germany
[2] APPEAL Engn UG haftungsbeschrankt, D-52066 Aachen, Germany
[3] FH Aachen Univ Appl Sci, D-52066 Aachen, Germany
[4] Dusseldorf Univ Appl Sci, Dept Mech & Proc Engn, D-40476 Dusseldorf, Germany
关键词
Indoor air quality; Indoor environmental quality; Energy-efficient ventilation; TVOC; Passive ventilation; CO2; PM2.5; CARBON-DIOXIDE; AIR-QUALITY; BUILDINGS; SCHOOL; TEMPERATURE; STRATEGIES; COMFORT; ROOMS;
D O I
10.1016/j.jobe.2024.110937
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this field study we present an approach for the comprehensive and room-specific assessment of parameters with the overall aim to realize energy-efficient provision of hygienically harmless and thermally comfortable indoor environmental quality in naturally ventilated non-residential buildings. The approach is based on (i) conformity assessment of room design parameters, (ii) empirical determination of theoretically expected occupant-specific supply air flow rates and corresponding air exchange rates, (iii) experimental determination of real occupant-specific supply air flow rates and corresponding air exchange rates, (iv) measurement of indoor environmental exposure conditions of T , RH , c CO 2 , c PM 2 . 5 and c TVOC , and (v) determination of real energy demands for the prevailing ventilation scheme. Underlying assessment criteria comprise the indoor environmental parameters of category II of EN 16798-1: Temperature T = 20 degrees C-24 degrees C, and relative humidity RH = 25 %-60 % as well as the guide values of the German Federal Environment Agency for c CO 2 c PM 2 . 5 and c TVOC of 1000 ppm, 15 mu g m- 3 , and 1 mg m- 3 , respectively. Investigation objects are six naturally ventilated classrooms of a German secondary school. Major factors influencing indoor environmental quality in these classrooms are the specific room volume per occupant and the window opening area. It is concluded that the rigorous implementation of ventilation recommendations laid down by the German Federal Environment Agency is ineffective with respect to anticipated indoor environmental parameters and inefficient with respect to ventilation energy losses on the order of about 10 kWh m- 2 a- 1 to 30 kWh m- 2 a- 1 .
引用
收藏
页数:19
相关论文
共 50 条
[21]   Specific Indoor Environmental Quality Parameters in College Computer Classrooms [J].
Chang, F. H. ;
Li, Y. Y. ;
Tsai, C. Y. ;
Yang, C. R. .
INTERNATIONAL JOURNAL OF ENVIRONMENTAL RESEARCH, 2009, 3 (04) :517-524
[22]   Indoor environmental quality in classrooms: Case studies [J].
SpringerBriefs in Applied Sciences and Technology, 2015, 146 :31-57
[23]   Indoor Air Quality in Naturally Ventilated Italian Classrooms [J].
Fuoco, Fernanda Carmen ;
Stabile, Luca ;
Buonanno, Giorgio ;
Trassiera, Concepcion Vargas ;
Massimo, Angelamaria ;
Russi, Aldo ;
Mazaheri, Mandana ;
Morawska, Lidia ;
Andrade, Alexandro .
ATMOSPHERE, 2015, 6 (11) :1652-1675
[24]   A ventilation intervention study in classrooms to improve indoor air quality: the FRESH study [J].
Rosbach, Jeannette T. M. ;
Vonk, Machiel ;
Duijm, Frans ;
van Ginkel, Jan T. ;
Gehring, Ulrike ;
Brunekreef, Bert .
ENVIRONMENTAL HEALTH, 2013, 12
[25]   Assessment of Indoor Environmental Quality for Retrofitting Classrooms with An Egg-Crate Shading Device in A Hot Climate [J].
Maria Calama-Gonzalez, Carmen ;
Suarez, Rafael ;
Luis Leon-Rodriguez, Angel ;
Ferrari, Simone .
SUSTAINABILITY, 2019, 11 (04)
[26]   Energy performance and indoor environmental quality in Hellenic schools [J].
Dascalaki, Elena G. ;
Sermpetzoglou, Vasileios G. .
ENERGY AND BUILDINGS, 2011, 43 (2-3) :718-727
[27]   Assessment of perceived indoor environmental quality, stress and productivity based on environmental sensor data and personality categorization [J].
Kallio, Johanna ;
Vildjiounaite, Elena ;
Koivusaari, Jani ;
Rasanen, Pauli ;
Simila, Heidi ;
Kyllonen, Vesa ;
Muuraiskangas, Salla ;
Ronkainen, Jussi ;
Rehu, Jari ;
Vehmas, Kaisa .
BUILDING AND ENVIRONMENT, 2020, 175
[28]   A comprehensive objective and subjective assessment survey of indoor environmental quality in higher education classrooms in a hot arid climate [J].
Al-Akhzami, Fatema ;
Al-Khatri, Hanan ;
Al-Saadi, Saleh ;
Khan, Hayder ;
Etri, Talal .
BUILDING AND ENVIRONMENT, 2024, 263
[29]   The effect of ventilation on the indoor environment quality in a natural ventilated office building, a case study [J].
Avgeilis, A. ;
Papadopoulos, A. M. .
Proceedings of the 8th International Conference on Environmental Science and Technology, Vol A, Oral Presentations, 2003, :44-51
[30]   Relationships between indoor environmental quality and environmental factors in university classrooms [J].
Yang, Da ;
Mak, Cheuk Ming .
BUILDING AND ENVIRONMENT, 2020, 186