Analysis of impact on voltage stability by starting synchronous condenser in Jeju AC network

被引:0
作者
Choi, Soon-Ho [1 ]
Lee, Seong-Doo [1 ]
Kim, Chan-Ki [1 ]
机构
[1] Power Transmission Laboratory, KEPCO Research Institute
关键词
HVDC transmission; Synchronous condenser; Voltage stability;
D O I
10.5370/KIEE.2015.64.1.023
中图分类号
TM72 [输配电技术];
学科分类号
摘要
Two old synchronous condensers in Jeju are being replaced by new machines to operate Jeju AC network with Haenam-Jeju HVDC system stably. Before new synchronous condensers operate on site, voltage stability analysis is conducted to verify stable operation of jeju AC network. Through impedance analysis of the synchronous machine, transformer and ac network, the equivalent circuit is constructed and the voltage drop during start-up is calculated. Then, PSS/E fault analysis is performed to acquire short-circuit capacity according to the generator operation scenarios. Voltage variation when starting synchronous condenser is simulated in PSCAD/EMTDC and satisfies the operating condition of jeju AC network and HVDC system. Copyright © The Korean Institute of Electrical Engineers.
引用
收藏
页码:23 / 28
页数:5
相关论文
共 7 条
[1]  
Jang B.H., Yoon J.S., Han J.Y., Shim J.W., Kang S.K., Lee B.J., The affections of system stability on replacing the synchronous condenser in jeju island, Transactions of the Korean Institute of Electrical Engineers, 56, 10, pp. 1715-1720, (2007)
[2]  
Kunder P., Power System Stability and Control, (1994)
[3]  
Jeju Synchronous Condenser Report, (2012)
[4]  
Horvath W.J., Concepts, configurations, & benefits of motor starting and operation with MV AC adjustable speed drives, IEEE-IAS Cement Industry Committee, (2008)
[5]  
Technical Note: Starting Methods for AC Motors, (2010)
[6]  
Larry B., Jim I., Starting Large Motors from an Onan Engine-generator Set, (1997)
[7]  
Lee S.Y., A Study on the Operating Strategies of Multi-infeed HVDC System Related to the Jeju Power System in the Future, (2013)