Passive Islanding Detection Method Based on Harmonic Voltage and Fundamental Frequency

被引:0
作者
Chen Y. [1 ]
Tang G. [1 ]
Wang S. [2 ]
Chen X. [1 ]
Wang X. [3 ]
Zhang Y. [4 ]
机构
[1] NARI Group Corporation, State Grid Electric Power Research Institute, Nanjing
[2] School of Automation, Nanjing University of Science and Technology, Nanjing
[3] State Grid Ningxia Electric Power Co. Ltd., Yinchuan
[4] State Grid Liaoning Electric Power Co. Ltd., Shenyang
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2019年 / 43卷 / 14期
基金
国家重点研发计划;
关键词
Fundamental frequency; Harmonic voltage; Islanding detection; Photovoltaic power station;
D O I
10.7500/AEPS20180914003
中图分类号
学科分类号
摘要
The existing passive islanding detection methods of independent anti-islanding protection device in photovoltaic power station have a large non-detection zone, and the frequency criterion is unable to distinguish between the power grid low frequency and the islanding low frequency. This paper proposes a new passive islanding detection method based on the harmonic voltage at point of common coupling (PCC) and the fundamental frequency. Firstly, the method is theoretically analyzed and the anti-misoperation measures are designed. Secondly, the method is simulated and validated under several conditions of islanding and grid-connected modes. Finally, the effectiveness of this method is verified by actual islanding data. The results show that the method is simple and reliable, which can not only narrow the non-detection zone, but also distinguish between the power grid low frequency and the islanding low frequency. © 2019 Automation of Electric Power Systems Press.
引用
收藏
页码:200 / 206
页数:6
相关论文
共 21 条
[1]  
Cheng Q., Wang Y., Cheng Y., Et al., Overview study on islanding detecting methods for distributed generation grid-connected system, Power System Protection and Control, 39, 6, pp. 147-154, (2011)
[2]  
Guo X., Wu W., Non-devastating islanding detection for microgrids without non-detection zone, Proceedings of the CSEE, 29, 25, pp. 7-12, (2009)
[3]  
Wang X., Freitas W., Impact of positive feedback anti-islanding methods on small-signal stability of inverter-based distributed Generation, IEEE Transactions on Energy Conversion, 23, 3, pp. 923-931, (2008)
[4]  
Liu F., Yu M., Zhang Y., Et al., Islanding detection evaluation for active frequency drifting methods in multiple photovoltaic grid-connected converters, Proceedings of the CSEE, 29, 12, pp. 47-51, (2009)
[5]  
Chen Z., Meng X., Wang X., Et al., A novel method of active low-frequency drift for islanding detection, Automation of Electric Power Systems, 38, 13, pp. 202-207, (2014)
[6]  
Lin M., Gu J., Shan Z., Et al., A practical hybrid islanding detection method for grid-connected photovoltaic system, Automation of Electric Power Systems, 33, 23, pp. 85-89, (2009)
[7]  
Ren B., Zhong Y., Sun X., Et al., Islanding detection method based on the alternate current disturbances, Automation of Electric Power Systems, 32, 19, pp. 81-84, (2008)
[8]  
Prasartsuwan K., Jirapong P., Analysis of islanding detection methods for grid-connected distributed generation in provincial electricity authority distribution systems, 9th International Conference on Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology
[9]  
Technical requirements for connecting photovoltaic power station to power system: GB/T 19964-2012, (2012)
[10]  
Liu J., Li Y., Dead-time influence on output error of voltage source inverter and compensation, Transactions of China Electrotechnical Society, 22, 5, pp. 117-122, (2007)