Analysis on grid-connectible capacity of distributed PV generation in case of PV generation distribution close to load distribution

被引:0
作者
Liu, Jian [1 ]
Huang, Wei [2 ]
机构
[1] Shaanxi Electric Power Research Institute, Xi'an, 710054, Shaanxi Province
[2] School of Electrical and Control Engineering, Xi'an University of Science and Technology, Xi'an, 710054, Shaanxi Province
来源
Dianwang Jishu/Power System Technology | 2015年 / 39卷 / 02期
关键词
Distributed photovoltaic generations; Distribution networks; Planning; Voltage deviation; Voltage fluctuation;
D O I
10.13335/j.1000-3673.pst.2015.02.001
中图分类号
学科分类号
摘要
To offer reasonable foundation for the planning of grid-connection of distributed photovoltaic (PV) generations, the mathematical models for voltage deviation and voltage fluctuation caused by various distributions of loads and PV generations are established. Taking the maximum upper deviation of voltage and the maximum voltage fluctuation caused by distributed PV generations and the maximum lower voltage deviation caused by the load only when the PV generation does not exist as constraints, the capacity range of allowed grid-connected distributed PV generations, by which the demand on voltage quality can be met under six distribution conditions of load and distributed PV generations along the feeder, is derived. Taking typical parameters of urban distribution network and those of rural distribution network for example, the proposed method is analyzed and illustrated, results of the analysis show that the proposed method is feasible, and using the proposed method the allowed grid-connected capacity range of distributed PV generations can be determined. ©, 2015, Power System Technology Press. All right reserved.
引用
收藏
页码:299 / 306
页数:7
相关论文
共 15 条
[1]  
Wang Z., Zhu S., Zhou S., Et al., Impact of distributed generation on the distribution system voltage profile, Automation of Electric Power Systems, 28, 16, pp. 56-60, (2004)
[2]  
Xu X., Huang Y., Liu C., Et al., Influence of distributed photovoltaic generation on voltage in distribution network and solution of voltage beyond limits, Power System Technology, 34, 10, pp. 140-146, (2010)
[3]  
Dong W., Bai X., Zhu N., Et al., Discussion on the power quality under grid-connection of intermittent power sources, Power System Technology, 37, 5, pp. 1265-1271, (2013)
[4]  
Yu J., Chi F., Xu K., Et al., Analysis of the impact of distributed generation on power grid, Proceedings of the CSU-EPSA, 24, 1, pp. 138-141, (2012)
[5]  
Ting M., Wang W., Wang X., Et al., A review on the effect of large-scale pv generation on power systems, Proceedings of the CSU-EPSA, 34, 1, pp. 1-14, (2014)
[6]  
Sjef C., Impact of photovoltaic generation on power quality in urban areas with high pv population
[7]  
Farid K., Integration of photovoltaic power systems in high-penetration clusters for distribution networks and mini-grids
[8]  
Zhao B., Zhang X., Hong B., Energy penetration of large-scale distributed photovoltaic sources integrated into smart distribution network, Electric Power Automation Equipment, 32, 8, pp. 95-100, (2012)
[9]  
Lei J., Huang W., Xia X., Et al., Penetration level calculation with considerations of phase-to-phase short circuit fault, Automation of Electric Power Systems, 32, 3, pp. 82-86, (2008)
[10]  
Lian X., Wu Z., Zhao K., Et al., Maximum penetration capacity calculation for distributed generation taking into account fault current constraints, Journal of Electric Power Science and Technology, 23, 1, pp. 50-55, (2008)