Energy-directional pilot protection based on leading-phase for active distribution network

被引:0
作者
Xu M. [1 ]
Zou G. [1 ]
Chen N. [2 ]
Zhang J. [2 ]
Ma Y. [1 ]
机构
[1] School of Electrical Engineering, Shandong University, Ji'nan
[2] State Gird Shandong Electric Power Company Zaozhuang Electric Power Company, Zaozhuang
来源
Dianli Zidonghua Shebei/Electric Power Automation Equipment | 2017年 / 37卷 / 01期
关键词
Active distribution network; Directional pilot protection; Distributed generator; Electric power system protection; Energy function; Fault component; Leading phase;
D O I
10.16081/j.issn.1006-6047.2017.01.010
中图分类号
学科分类号
摘要
Based on the characteristic analysis of fault-phase energy function for different fault types, a method of energy-directional pilot protection is proposed. According to the characteristics of distribution network with ineffectively-grounded neutral point, a fault recognition criterion based on the leading-phase is established and an auxiliary criterion based on the amplitude of energy function is added to get over the impact of in-zone branch load switching on the fault recognition. Its adaptability to the distributed generators which are connecting with the distribution network via inverter based on the positive-sequence component control is studied. Simulative results show the proposed method is immune to the transition resistance to a certain extent and able to recognize the fault directions correctly and get over the impact of load switching. © 2017, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:58 / 64
页数:6
相关论文
共 15 条
[11]  
Gao H., Li J., Zhu G., Et al., Study on application technology of current differential protection in active distribution network, Power System Protection and Control, 42, 5, pp. 40-44, (2014)
[12]  
Liu H., Wang Z., Liu H., Et al., Improved energy directional protection and its application in UHV transmission lines, Power System Technology, 34, 10, pp. 185-191, (2010)
[13]  
Tan H., Li Y., Chen X., Et al., Influence of inverter-interfaced distributed generator with low-voltage ride-through capability on short circuit current of distribution network, Electric Power Automation Equipment, 35, 8, pp. 31-37, (2015)
[14]  
Wu Z., Wang G., Li H., Et al., Analysis on the distribution network with distributed generators under phase-to-phase short-circuit faults, Proceedings of the CSEE, 33, 1, pp. 130-136, (2013)
[15]  
Han H., Mu L., Guo W., Adaptability of microgrid protection based on fault components, Automation of Electric Power Systems, 40, 3, pp. 90-96, (2016)