Research on Improved Control Strategies of STATCOM for LCC-HVDC Weak Receiving Station

被引:0
|
作者
Yao W. [1 ]
Liu G. [1 ]
Hu S. [1 ]
Sun J. [1 ]
Zuo G. [1 ]
Xu E. [1 ]
Gao Z. [1 ]
机构
[1] Xuji Group Corporation, Xuchang, 461000, Henan Province
来源
| 2018年 / Chinese Society for Electrical Engineering卷 / 38期
关键词
Individual phase instantaneous current control; Line commutate converter based high voltage direct current (LCC-HVDC); Static synchronous compensator (STATCOM); Transient individual phase control; Voltage feedforward;
D O I
10.13334/j.0258-8013.pcsee.171295
中图分类号
学科分类号
摘要
This paper studied the control strategies of static synchronous compensator (STATCOM) for the weak receiving station of line commutate converter based high voltage direct current (LCC-HVDC) transmission system, to improve its transient control characteristics. First, the individual phase instantaneous current control strategy based on proportional resonance controller was discussed. Second, the short-circuit impedance of the dedicated transformer was equivalent to the main circuit of STATCOM, then STATCOM was equivalent to hanging directly in the virtual 35 kV AC system. The instantaneous value feedforward of virtual 35 kV voltage and its on-line switching method with 35 kV voltage amplitude feedforward were proposed and a transient individual phase control strategy with virtual 35 kV voltage as the control target was proposed. Finally, the simulation results, RTDS test and engineering field test verify the rationality and validity of the proposed control strategies in the first set of STATCOM applied to LCC-HVDC weak receiving station in China. © 2018 Chin. Soc. for Elec. Eng.
引用
收藏
页码:3662 / 3670
页数:8
相关论文
共 20 条
  • [1] Wei W., Song Q., Teng L., Et al., Research on anti-fault dynamic control of static synchronous compensator using cascade multilevel inverters, Proceedings of the CSEE, 25, 4, pp. 19-24, (2005)
  • [2] Yuan Z., Research on the control and protect schemes of STATCOM using cascade multilevel inverter, (2006)
  • [3] Liu Z., Liu B., Duan S., Et al., Research on cascade multilevel STATCOM under unbalanced system voltage, Proceedings of The CSEE, 31, 9, pp. 1-7, (2011)
  • [4] Xiong Q., Luo A., Ma F., Et al., A reference current detection method of delta-connected cascaded SVG considering unbalance compensation, Proceedings of the CSEE, 33, 27, pp. 12-19, (2013)
  • [5] Mei H., Liu J., Circulating current control of the delta-connected cascaded STATCOM, Proceedings of the CSEE, 34, 36, pp. 6398-6406, (2014)
  • [6] He Z., Luo A., Ma F., Et al., Control method for delta-connected cascaded SVG under unbalanced condition, Proceedings of the CSEE, 36, 14, pp. 3878-3887, (2016)
  • [7] Xu S., Chen M., Fu C., Et al., The system commissioning of ±200 Mvar STATCOM in China southern power grid, Southern Power System Technology, 6, 2, pp. 21-25, (2012)
  • [8] Li C., Huang W., Yuan Z., Et al., Systematic control strategies for ±200 Mvar cascaded STATCOM in China southern power grid, Automation of Electric Power Systems, 37, 3, pp. 116-121, (2013)
  • [9] Zhou B., Hong C., Jin X., Et al., Study of backbone structure change from synchronous to asynchronous in china southern power grid, Procee- dings of the CSEE, 36, 8, pp. 2084-2092, (2016)
  • [10] Zhao Y., Hong C., Zeng Y., Et al., The voltage support strength factor(VSG) for multi-infeed HVDC systems and its application in CSG’s STATCOM allocation scheming, Southern Power System Technology, 8, 4, pp. 22-26, (2014)