Substation Information Based Method for Preventing Mal-operation of Zero-sequence Directional Protection on Multi-circuit Transmission Lines on the Same Tower

被引:0
|
作者
Dai F. [1 ]
Wang X. [1 ]
Yang G. [1 ]
Zhou Z. [1 ]
机构
[1] China Electric Power Research Institute, Beijing
关键词
Asymmetric longitudinal fault; Mal-operation prevention; Multi-circuit transmission lines on the same tower; Zero-sequence directional protection; Zero-sequence voltage compensation;
D O I
10.7500/AEPS20180825004
中图分类号
学科分类号
摘要
In case of open-phase operation or asymmetric longitudinal fault occurring on one line of the multi-circuit transmission lines on the same tower, the zero-sequence directional protection of healthy lines with the same voltage on the same tower may mal-operate due to the zero-sequence voltage compensation. Zero-sequence voltage induced between the lines on the same tower with mixed voltages may also cause mal-operation. The electrical characteristics of asymmetric longitudinal faults and open-phase operation and the specific mechanism leading to mal-operation of zero sequence directional protection are analyzed. The influence of various factors on the process of mal-operation and the solution are discussed. A method for preventing mal-operation by extracting the states of transmission lines based on substation information is proposed. For multi-circuit transmission lines with the same voltage on the same tower, the method for preventing mal-operation by calculating the cross point of zero-sequence voltage and reversely compensating zero-sequence voltage is proposed. For multi-circuit transmission lines on the same tower with the mixed voltages, the method of identifying the failure characteristics of the lines based on the substation information and automatically blocking the zero-sequence directional protection is proposed. Real-time digital simulator (RTDS) is used to simulate the electrical characteristics of healthy lines and the mal-operation process when an asymmetric longitudinal/latitudinal fault occurs on multi-circuit transmission lines on the same tower under different work conditions. The effectiveness of the proposed method for preventing mal-operation is verified. © 2019 Automation of Electric Power Systems Press.
引用
收藏
页码:131 / 138
页数:7
相关论文
共 21 条
  • [1] Lin F., Wang Z., Fault locating method based on two-terminal common positive sequence fundamental frequency component for parallel transmission line, Proceedings of the CSEE, 31, 4, pp. 93-98, (2011)
  • [2] Zou Y., Chen W., Li S., Et al., Quasi-three-phase operation and tripping and reclosing strategy of double-circuit transmission lines on the same tower, Automation of Electric Power Systems, 39, 15, pp. 137-142, (2015)
  • [3] Zhang C., Li Y., Zeng G., Principle investigation and simulation research on pilot zero sequence directional protection with compensation of negative sequence component, Power System Protection and Control, 36, 21, pp. 18-23, (2008)
  • [4] Song G., Xu H., Fan Z., Et al., A method for preventing mal-operation of zero-sequence direction component using current fault component, Automation of Electric Power Systems, 40, 2, pp. 114-120, (2016)
  • [5] Lai Q., Chen F., Xu Q., Et al., Analysis of pilot zero-sequence directional protection special problems and solutions, Electric Power Automation Equipment, 30, 12, pp. 88-91, (2010)
  • [6] Xu Z., Du Z., Meng Y., Et al., Special problems in zero/negative sequence directional element, Electric Power Automation Equipment, 28, 5, pp. 21-25, (2008)
  • [7] Xu H., Huang X., Wang T., Et al., Analysis of zero-sequence voltage compensation in double-circuit transmission system, Power System Protection and Control, 45, 4, pp. 86-92, (2017)
  • [8] Xu H., Song G., Fan Z., Et al., A novel method adapted to weak-infeed system for preventing mal-operation of the zero-sequence direction component, Power System Technology, 39, 10, pp. 2952-2958, (2015)
  • [9] Tian B., Zhang T., Chen J., Et al., Analysis of influence of unbalanced zero-sequence current on pilot zero-sequence protection and its countermeasures, Automation of Electric Power Systems, 37, 19, pp. 132-135, (2013)
  • [10] Zhang Q., Improvement of zero-sequence directional component for parallel lines with magnetically strong and electrically weak connection, Automation of Electric Power Systems, 37, 7, pp. 94-98, (2013)