Improved Bergeron Model of Power Cable Considering Parameter Frequency-dependent Characteristics

被引:0
|
作者
Wang H. [1 ]
Cao S. [1 ]
Feng M. [1 ]
Xu J. [1 ]
机构
[1] State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources (North China Electric Power University), Changping District, Beijing
基金
中国国家自然科学基金;
关键词
Bergeron model; frequency-dependent characteristics; parameter calculation of power cable; power cable modeling;
D O I
10.13334/j.0258-8013.pcsee.223455
中图分类号
学科分类号
摘要
The interaction between power electronic equipment, renewable energy units and power grids in the new power system leads to broadband resonance problems. Power cables are key links of renewable energy integration and their non-negligible distributed capacitance increases the risk of broadband resonance. The existing research mainly includes time-domain simulation and impedance analysis. However, the distributed parameter characteristics and frequency-dependent characteristics are ignored during the modeling, which leads to inaccurate stability assessment, lower efficiency of simulation and imaginary oscillation. The traditional Bergeron model fails to take the frequency-dependent characteristics into consideration, which causes problems like high-order harmonic amplification. In order to determine the modeling method suitable for power cables in the harmonic frequency range, the simplified calculation of power cable parameters is summarized according to the cable structure. On this basis, the advantages of Bergeron model are explored deeply, and the cable electrical parameters are modified according to the related harmonic frequency to improve the traditional Bergeron mode. Finally, the results obtained by the simplified calculation method of power cable electrical parameters are compared with those obtained by the calculation in PSCAD/EMTDC, and the proposed improved model is tested in time domain to verify its correctness and effectiveness. © 2024 Chin.Soc.for Elec.Eng.
引用
收藏
页码:3722 / 3731
页数:9
相关论文
共 27 条
  • [1] CHI Yongning, LIANG Wei, ZHANG Zhankui, An overview on key technologies regarding power transmission and grid integration of large scale offshore wind power[J], Proceedings of the CSEE, 36, 14, pp. 3758-3770, (2016)
  • [2] WANG Xifan, WEI Xiaohui, NING Lianhui, Integration techniques and transmission schemes for off-shore wind farms[J], Proceedings of the CSEE, 34, 31, pp. 5459-5466, (2014)
  • [3] SAAD H,, FILLION Y, DESCHANVRES S, On resonances and harmonics in HVDC-MMC station connected to AC grid[J], IEEE Transactions on Power Delivery, 32, 3, pp. 1565-1573, (2017)
  • [4] XIE Xiaorong, LIU Huakun, HE Jingbo, On new oscillation issues of power systems[J], Proceedings of the CSEE, 38, 10, pp. 2821-2828, (2018)
  • [5] ZHANG Shao, JIANG Shuai, LU Xi, Resonance issues and damping techniques for grid-connected inverters with long transmission cable[J], IEEE Transactions on Power Electronics, 29, 1, pp. 110-120, (2014)
  • [6] WANG Xiaotong, XIANG Zutao, BAN Liangeng, Calculation and analysis on power-frequency parameters for 500 kV cable lines[J], Power System Technology, 37, 8, pp. 2310-2315, (2013)
  • [7] WANG Xiaotong, XIANG Zutao, CHEN Zhenzhen, Analysis on electrical parameters and its unbalance factors for 500 kV XLPE submarine cable lines[J], Power System Technology, 42, 11, pp. 3812-3819, (2018)
  • [8] Zheng XU, LI Sixun, JIN Yanqiu, Calculation of electrical parameters of submarine cable in harmonic frequency range[J], Automation of Electric Power Systems, 45, 21, pp. 76-84, (2021)
  • [9] Zheng XU, QIAN Jie, Comparison of different methods for calculating electrical parameters of power cables [J], High Voltage Engineering, 39, 3, pp. 689-697, (2013)