The Design of Three Phase Frequency Locked Loop Based on Linear Kalman Filter

被引:0
作者
Dou X. [1 ]
Jiao Y. [1 ]
Quan X. [1 ]
Li N. [2 ]
Wu Z. [1 ]
机构
[1] Jiangsu Key Laboratory of Smart Grid Technology and Equipment (Southeast University), Nanjing, 210096, Jiangsu
[2] Nari Group Corporation, Nanjing, 210096, Jiangsu
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2019年 / 39卷 / 03期
基金
中国国家自然科学基金;
关键词
DC bias component; Frequency locked loop; Grid synchronization algorithm; Kalman filter; Three phase system;
D O I
10.13334/j.0258-8013.pcsee.172756
中图分类号
学科分类号
摘要
The effectiveness of grid synchronization algorithm is of great importance to improve the performance of grid-connected controller. A three-phase frequency-locked- loop based on linear Kalman filter (LKF-FLL) was proposed. Firstly, the validity of Kalman filter for orthogonal decomposition of voltage distortion signal with DC bias was analyzed. The analysis shows that when the frequency is a known quantity, the linear Kalman filter can be used to estimate the grid status, including frequency, positive / negative sequence and DC bias. Then the adaptive three-phase frequency-locked-loop structure was proposed through error analysis for the fundamental frequency observation. Next, using the state observer's idea to design cost function for the optimal gain coefficient, and inversely calculate Kalman filter parameters, which can avoid choosing the filter parameters according to experience only. Finally, by comparing with the existing technology, such as second-order generalized integrator (SOGI), adaptive victoria filter (AVF), the effectiveness and superiority of the proposed three-phase FLL were shown in the case of distorted three-phase voltage with DC bias. © 2019 Chin. Soc. for Elec. Eng.
引用
收藏
页码:832 / 844
页数:12
相关论文
共 24 条
  • [11] Wang D., Liu W., Guo X., Et al., Grid synchronization technique with high-order decoupled complex filters for grid-connected converters under non-ideal grid voltages, Proceedings of the CSEE, 35, 10, pp. 2576-2583, (2015)
  • [12] Tang Y., Xie Y., Wang Y., Et al., Study on PLL based on decoupled double synchronous reference frame, Electrical Measurement & Instrumentation, 54, 8, pp. 14-20, (2017)
  • [13] Deng Z., Zhou F., Lin H., Et al., A novel fast grid-synchronization method under grid failure based on dual-input SOGI-FLL, Transactions of China Electrote-chnical Society, 28, 12, pp. 32-43, (2013)
  • [14] Rodriguez P., Luna A., Candela I., Et al., Multiresonant frequency-locked loop for grid synchronization of power converters under distorted grid conditions, IEEE Transactions on Industrial Electronics, 58, 1, pp. 127-138, (2011)
  • [15] Vazquez S., Sanchez J.A., Reyes M.R., Et al., Adaptive vectorial filter for grid synchronization of power converters under unbalanced and/or distorted grid conditions, IEEE Transactions on Industrial Electronics, 61, 3, pp. 1355-1367, (2014)
  • [16] Reza S., Ciobotaru M., Agelidis V.G., Accurate estimation of single-phase grid voltage fundamental amplitude and frequency by using a frequency adaptive linear Kalman filter, IEEE Journal of Emerging and Selected Topics in Power Electronics, 4, 4, pp. 1226-1235, (2016)
  • [17] Yazdanian M., Mojiri M., Sheikholeslam F., An extended Kalman filter for identification of biased sinusoidal signals, Proceedings of the 20th Iranian Conference on Electrical Engineering (ICEE2012), (2012)
  • [18] Hajimolahoseini H., Taban M.R., Abutalebi H.R., Improvement of Extended Kalman Filter frequency tracker for nonstationary harmonic signals, Proceedings of 2008 International Symposium on Telecommunications, (2008)
  • [19] Sun M., Sahinoglu Z., Extended Kalman filter based grid synchronization in the presence of voltage unbalance for smart grid, Proceedings of ISGT 2011, (2011)
  • [20] Chen C.I., Chang G.W., Hong R.C., Et al., Extended real model of Kalman Filter for time-varying harmonics estimation, IEEE Transactions on Power Delivery, 25, 1, pp. 17-26, (2010)