Characteristic Analysis and Fault Segment Location on Negative Sequence Voltage and Current of Single Phase Line Breakage Fault in Distribution Network

被引:0
作者
Chang Z. [1 ]
Song G. [1 ]
Zhang W. [1 ]
机构
[1] Shaanxi Key Laboratory of Smart Grid, Xi'an Jiaotong University, Xi'an, 710049, Shaanxi Province
来源
Dianwang Jishu/Power System Technology | 2020年 / 44卷 / 08期
关键词
Distribution network; Fault segment location; Feeder automation; Negative sequence network; Single-phase line breakage fault;
D O I
10.13335/j.1000-3673.pst.2019.1830
中图分类号
学科分类号
摘要
Single-phase line breakage fault may cause accidents such as overvoltage, personal injury, motor damage. Aiming to reduce the difficulty in finding such faults, a novel single-phase line breakage fault detection method based on correlation coefficient of negative sequence voltage and current is proposed. The relationship between the phases of the negative sequence voltage and current is analyzed based on the negative sequence network firstly. It points out that the correlation coefficients of the negative sequence voltage and current of segments located at the upstream of the fault point are negative, while those for segments located at the downstream of fault point, on the healthy lines and on the parallel branches of the faulty line are positive. Finally, location and isolation method of the single-phase line breakage fault is proposed based on the local type feeder automation mode, intelligent distributed feeder automation mode and centralized fault automation moderespectively. Theoretical analysis and PSCAD-based simulations show that the proposed single-phase line breakage fault detection method is immune to neutral grounding mode, power factor, transition resistance and single phase line breakage fault types. Meanwhile, forthatonlylogic signalsneed to be transmitted when combined with the intelligent distributed or centralized feeder automation modes, the communication burden isrelatively low. © 2020, Power System Technology Press. All right reserved.
引用
收藏
页码:3065 / 3072
页数:7
相关论文
共 28 条
[1]  
Wang Maocheng, LuYongli, ZouHongying, Et al., Analysis of lightning-caused break mechanism of 10 kV insulation-covered conductors and its countermeasures, High Voltage Engineering, 33, 1, pp. 102-105, (2007)
[2]  
Li Zhenkun, Zhao Xiangyang, Zhu Lan, Et al., Evaluation of self-healing ability for smart distribution network after failure, Power System Technology, 42, 3, pp. 789-796, (2018)
[3]  
Lin Chunqing, Li Chunping, GuoZhaocheng, Et al., Analysis and discrimination on overvoltage in arc suppression coil earthed system caused by loaded line breakage, Power System Technology, 36, 9, pp. 275-280, (2012)
[4]  
Kalyuzhny A., Analysis of temporary overvoltages during open-phase faults in distribution networks with resonant grounding, IEEE Transactions on Power Delivery, 30, 1, pp. 420-427, (2015)
[5]  
Wang Qinghua, Analysis of distribution line break failure, Guangxi Water Resources & Hydropower Engineering, 6, pp. 57-60, (2011)
[6]  
Dai Zhihui, Wang Xu, Impedance method based fault location algorithm for active distribution system, Power System Technology, 41, 6, pp. 2027-2034, (2017)
[7]  
He Ruijiang, Hu Zhijian, Li Yan, Et al., Fault section location method for DG-DNs based on integer linear programming, Power System Technology, 42, 11, pp. 3684-3692, (2018)
[8]  
Chang Zhongxue, Song Guobing, Huang Wei, Et al., Phase voltage and current fault components based fault segment location method under single-phase earth fault in distribution network, Power System Technology, 41, 7, pp. 2363-2370, (2017)
[9]  
Liu Jian, Zhang Xiaoqing, Li Pinde, Et al., A novel approach treating single-phase ground fault in distribution system, Power System Technology, 40, 11, pp. 3586-3590, (2016)
[10]  
Wang Shilin, Liu Zhu, Zhang Zhe, Et al., Research on single phase grounding fault detection technology of distribution network based on intelligent variable terminal, Power System Technology, 43, 12, pp. 4291-4298, (2019)