Dielectric loss monitoring digital algorithm for solid-insulated ring main unit

被引:0
作者
机构
[1] School of Electrical Engineering, Shenyang University of Technology
来源
Cao, Y. (caoyundong@hotmail.com) | 1600年 / Science Press卷 / 40期
关键词
Capacitive current; Dielectric loss; Instantaneous power transform; Orthogonal decomposition; Resistive current; Solid-insulated ring main unit;
D O I
10.13336/j.1003-6520.hve.2014.05.025
中图分类号
学科分类号
摘要
Dielectric loss online monitoring system for solid-insulated sleeves in solid-insulated ring main unit has disadvantages of its poor anti-interference ability, strict synchronous sampling criterion and low calculation resolution, which may affect its monitoring precision. To reduce this influence, we proposed to apply instantaneous power transform theory to obtain dielectric loss and instantaneously extract resistive current and capacitive current by signal decomposition, hence to realize dynamic dielectric loss monitoring. Combined with an improved filter design, high precision of the monitoring was achieved. We also designed and established a monitoring system to test our design. The results show that the system can manage its relative online monitoring error within 3%, and the proposed method can effectively reduce the error due to spectral leakage and fence effect which are caused by asynchronous and non-integral period sampling.
引用
收藏
页码:1468 / 1474
页数:6
相关论文
共 26 条
  • [1] Q/GDW 730-2012 Specifications for 12 kV solid-insulated ring main units, (2012)
  • [2] Kong X., Zhao S., Jia H., Et al., Analysis of equipment and technology in smart grid development, Proceedings of the CSU-EPSA, 24, 2, pp. 21-26, (2012)
  • [3] Chen W., Wang H., Wang Z., Et al., Withstand characteristics analysis of inductive voltage transformer in UHV gas insulated switchgear under very fast transient overvoltage, High Voltage Engineering, 39, 6, pp. 1402-1410, (2013)
  • [4] Liu S.X., Cao Y.D., Hou C.G., Et al., Development of on-line monitoring system of switchgear, International Conference on Electric Power Equipment-Switching Technology, pp. 295-298, (2011)
  • [5] Wang K., Cai W., Deng Y., Et al., Application and management information platform for transmission line monitoring system, High Voltage Engineering, 38, 5, pp. 1274-1280, (2012)
  • [6] Shen W., Ke C., Wang H., Et al., Multi-parameter diagnosis of HVDC bushing, High Voltage Engineering, 38, 3, pp. 616-622, (2012)
  • [7] Li T., Fan X., Wang J., Et al., A method to detect dielectric loss factor based on wavelet filtering and tracking differentiator, Power system technology, 35, 4, pp. 223-226, (2011)
  • [8] Du L., Huang X., Sima W., Et al., Analysis on power grid voltage frequency measurement method based on leakage current of capacitive equipment, High Voltage Engineering, 38, 6, pp. 1307-1315, (2012)
  • [9] Xie X., Hu W., Peng Z., Et al., Dielectric loss characteristics of 550 kV resin-impregnated paper oil-SF<sub>6</sub> bushing during thermal-stabilization testing, High Voltage Engineering, 38, 10, pp. 2749-2754, (2012)
  • [10] Wang H., Huang X., Wang H., Et al., Design of an on-line monitoring IED of dielectric loss in capacitive equipment in intelligent substation, High Voltage Apparatus, 48, 1, pp. 1-7, (2012)