Self-starting strategy of variable speed pumped storage units in pumping mode

被引:0
作者
Shao Y. [1 ]
Ji L. [1 ,2 ]
Yuan Y. [2 ]
Gao S. [3 ]
机构
[1] NARI Group Corporation (State Grid Electric Power Research Institute), Nanjing
[2] College of Energy and Electrical Engineering, Hohai University, Nanjing
[3] State Grid Xinyuan Company Limited, Beijing
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2016年 / 40卷 / 24期
关键词
Mechanical characteristic; Pumped storage; Self-starting; Variable speed constant frequency;
D O I
10.7500/AEPS20160816008
中图分类号
学科分类号
摘要
This paper focuses on the self-starting strategy of variable speed pumped storage units (VSPSU) by the shorting machine stator. Firstly, the mathematical model, phasor diagram and characteristics of VSPSU are proposed while the machine stator is being short-circuited. Then a robust stator flux observer is created for the self-starting strategy with stator flux oriented control to accelerate the rotor for synchronization. The starting time, torque characteristics and estimated accuracy of this strategy are quantitatively analyzed by simulation. The results show that the strategy has good starting performance and robustness. © 2016 Automation of Electric Power Systems Press.
引用
收藏
页码:125 / 130
页数:5
相关论文
共 17 条
  • [11] Pannatier Y., Kawkabani B., Simond J.J., Investigation of control strategies for variable-speed pump-turbine units by using a simplified model of the converters, IEEE Trans on Industrial Electronics, 57, 9, pp. 3039-3049, (2010)
  • [12] Song Z., Wang X., Teng Y., Et al., Overview of control technologies for variable-speed constant-frequency wind turbines, Automation of Electric Power Systems, 34, 10, pp. 8-17, (2010)
  • [13] Cao J., Wang H., Qiu J., Frequency control strategy of variable-speed constant-frequency doubly-fed induction generator wind turbines, Automation of Electric Power Systems, 33, 13, pp. 78-82, (2009)
  • [14] Wang D., Yang B., Li G., Et al., A control strategy of static frequency converter start-up for pump-storage power plants without position sensors, Automation of Electric Power Systems, 36, 23, pp. 114-119, (2012)
  • [15] Morel L., Godfroid H., Mirzaian A., Et al., Double-fed induction machine: converter optimization and field oriented control without position sensor, IEE Proceedings: Electric Power Applications, 145, 4, pp. 360-368, (1998)
  • [16] Pannatier Y., Kawkabani B., Nicolet C., Et al., Start-up and synchronization of a variable speed pump-turbine unit in pumping mode, 19th International Conference on Electrical Machines
  • [17] Pannatier Y., Kawkabani B., Nicolet C., Et al., Optimization of the start-up time of a variable speed pump-turbine unit in pumping mode, 20th International Conference on Electrical Machines, pp. 2126-2132