Establishment of preventive measures against faults based on the area of severity to voltage sags

被引:0
作者
Park, Chang-Hyun [2 ]
Lee, Kyebyung [3 ]
Lee, Hansang [4 ]
Yoon, Dong-Hee [1 ]
机构
[1] Depart. of New and Renewable Energy, Kyungil University
[2] Depart. of Electrical Engineering, Pukyong National University
[3] School of Electrical Engineering, Korea University
[4] School of Electrical and Railway Engineering, Kyungil University
关键词
Area of severity(AOS); Area of vulnerability(AOV); Power quality; Voltage sag mitigation; Voltage sags;
D O I
10.5370/KIEE.2015.64.11.1611
中图分类号
学科分类号
摘要
This paper presents an effective approach for establishing countermeasures against voltage sags based on the concept of area of severity. In order to apply preventive measures against faults such as lightning arrester, overhead earth wires and so on, it is important to find optimal points for installing the preventive measures. The optimal points can be determined by the calculation of the area of severity(AOS) to voltage sags and the expected sag frequency per unit length of line. In this paper, an effective method to find optimal points to apply countermeasures against voltage sags is addressed with case studies. © Copyright The Korean Institute of Electrical Engineers.
引用
收藏
页码:1611 / 1617
页数:6
相关论文
共 8 条
[1]  
Bollen M.H.J., Understanding Power Quality Problems: Voltage Sags and Interruptions
[2]  
Dugan R.C., McGranaghan M.F., Santoso S., Beaty H.W., Electrical Power Systems Quality., (2002)
[3]  
Goswami A.K., Gupta C.P., Singh G.K., Voltage sag assessment in a large chemical industry, IEEE Trans. Ind. Appl., 48, 5, pp. 1739-1746, (2012)
[4]  
Park C.H., Jang G., Stochastic estimation of voltage sags in a large meshed network, IEEE Trans. Power Del., 22, 3, pp. 1655-1664, (2007)
[5]  
Qader M.R., Bollen M.H.J., Allan R.N., Stochastic prediction of voltage sags in a large transmission system, IEEE Trans. Ind. Appl., 35, 1, pp. 152-162, (1999)
[6]  
Bollen M.H.J., Fast assessment methods for voltage sags in distribution systems, IEEE Trans. Ind. Appl., 32, 6, pp. 1414-1423, (1996)
[7]  
Conrad L., Little K., Grigg C., Predicting and preventing problems associated with remote fault-clearing voltage dips, IEEE Trans. Ind. Appl., 27, 1, pp. 167-172, (1991)
[8]  
Park C.H., Hong J.H., Jang G., Assessment of system voltage sag performance based on the concept of area of severity, IET Gener. Transm. Distrib., 4, 6, pp. 683-693, (2010)