Battery energy storage power supply simulation model for power grid frequency regulation

被引:0
|
作者
College of Electrical and Information Engineering, Hunan University, Changsha [1 ]
410082, China
机构
[1] College of Electrical and Information Engineering, Hunan University, Changsha
来源
Dianli Xitong Zidonghue | / 18卷 / 20-24 and 74期
基金
中国国家自然科学基金;
关键词
Electro-magnetic transient (EMT); Frequency regulation; LiFePO[!sub]4[!/sub; Simulation;
D O I
10.7500/AEPS20141012002
中图分类号
学科分类号
摘要
A battery energy storage power supply model for power grid frequency regulation is studied. First, the output characteristics of battery energy storage power are obtained by analyzing the amplitude and charge-discharge frequency characteristics in frequency regulation conditions. Then the process of constructing an electro-magnetic transient (EMT) model of battery energy storage power is presented, based on which a digital simulation model adapted to the needs of frequency regulation research and its parameter identification method are proposed. Finally, based on the multiple sets of experimental data of LiFePO4 batteries, the parameters of the simulation model are identified using an improved genetic algorithm and verified in frequency regulation scenarios. The validation results show that the simulation data of the model fit the actual operating data of the energy storage power with an error less than 1%, and the proposed simulation model has a rational structure that is able to meet the simulation requirements of primary and secondary frequency regulation as well as other applications on a second-minute timescale. ©, 2015 Automation of Electric Power Press.
引用
收藏
页码:20 / 24and74
页数:2454
相关论文
共 10 条
  • [1] Chen D., Zhang L., Wang S., Et al., Development of energy storage in frequency regulation market of United States and its enlightenment, Automation of Electric Power Systems, 37, 1, pp. 9-13, (2013)
  • [2] Gao M., Hui D., Gao Z., Et al., Presentation of national wind/photovoltaic/energy storage and transmission demonstration project and analysis of typical operation modes, Automation of Electric Power Systems, 37, 1, pp. 59-64, (2013)
  • [3] Liu L., Liu R., Li W., Development of dynamic simulation system for frequency regulation of interconnected power grids, Power System Technology, 33, 7, pp. 36-41, (2009)
  • [4] Chen M., Rincon G.A., Mora accurate electrical battery model capable of predicting runtime and I-V performance, IEEE Trans on Energy Conversion, 21, 2, pp. 504-511, (2006)
  • [5] Pillai J.R., Jensen B.B., Integration of vehicle-to-grid in the western Danish power system, IEEE Trans on Sustainable Energy, 2, 1, pp. 12-19, (2011)
  • [6] Wang H., Tang Y., Hou J., Et al., Composition modeling and equivalence of an integrated power generation system of wind, photovoltaic and energy storage unit, Proceedings of the CSEE, 31, 34, pp. 1-9, (2011)
  • [7] Li Y., Jing P., Wang L., Et al., A mathematical model of versatile energy storage system and its modeling by power system analysis software package, Power System Technology, 36, 1, pp. 51-57, (2012)
  • [8] Huang Y., Liu J., Chen J., Et al., Load frequency control considering vehicle to grid, Automation of Electric Power Systems, 36, 9, pp. 24-28, (2012)
  • [9] Ding M., Chen Z., Su J., Et al., An overview of battery energy storage for renewable energy generation, Automation of Electric Power Systems, 37, 1, pp. 19-25, (2013)
  • [10] Wang L., Li X., Ma Y., Et al., Dynamic model of fuel cell power generating system, Proceedings of the CSEE, 31, 22, pp. 40-47, (2011)