Failure aspects of electronic watt-hour meters due to direct lightning strikes to distribution lines - Electromagnetic disturbance caused by lightning current flowing through watt-hour meters and its countermeasure-

被引:0
|
作者
Ishimoto K. [1 ,2 ]
Mori R. [1 ]
Asakawa A. [1 ]
Ohki Y. [2 ]
机构
[1] Electric Power Engineering Research Laboratory, CRIEPI, 2-6-1, Nagasaka, Yokosuka
[2] Department of Electrical Engineering and Bioscience, Waseda University, 3-4-1, Okubo, Shinjuku-ku, Tokyo
来源
Ishimoto, Kazuyuki (ishimoto@criepi.denken.or.jp) | 1600年 / Institute of Electrical Engineers of Japan卷 / 137期
关键词
Distribution lines; Failure rate calculation; Lightning protection countermeasure; Smart meter; Transient magnetic field;
D O I
10.1541/ieejpes.137.766
中图分类号
学科分类号
摘要
Recently, advanced "smart meters" have been introduced widely to electric power distribution lines. Since smart meters consist of many low-voltage electronic devices, their vulnerability to disturbances such as lightning surges is a matter of concern. Therefore, to establish an effective lightning protection countermeasure against these disturbances, we have been investigating the lightning failure aspects of electronic watt-hour meters (WHMs), which have a function similar to that of a watt-meter section in smart meters. In this paper, we explored countermeasures for improving the performance of WHMs against the lightning transient magnetic fields. At first, we examined the performance of WHMs by lightning impulse current tests. As a result, it has become clear that the increase in distance between a bus conductor and a processing unit and magnetic shield of a processing unit are effective in reducing the probability of failures caused by the transient magnetic fields. Next, we proposed a calculation method of the lightning failure rate of WHMs based on a lightning surge analysis. The calculation results indicate that the failure occurs more frequently by subsequent strokes than by first strokes or if the grounding resistance of a pole transformer is higher. © 2017 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:766 / 776
页数:10
相关论文
共 3 条
  • [1] Precision current transformers for electronic watt-hour meters
    Ferch, Martin
    Components, 1998, 33 (06): : 37 - 38
  • [2] Estimation of Damage Rate of Electronic Watt-Hour Meters Caused by Transient Magnetic Field due to Direct Lightning Strokes to Distribution Line
    Ishimoto, Kazuyuki
    Mori, Ryota
    Asakawa, Akira
    2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2016,
  • [3] Investigation on lightning surge current flows from residential solar power system to distribution lines and watt-hour meters
    Ishii, Tsunayoshi
    Takami, Jun
    Okabe, Shigemitsu
    IEEJ Transactions on Power and Energy, 2014, 134 (08) : 724 - 731