摘要
The widespread integration of various nonlinear power electronic devices in modern power systems has made harmonic distortion more serious than ever before. Given the urgent need to improve power quality, the harmonic contribution evaluation (HCE) is of great importance since it can provide a strong basis for harmonic mitigation measures. However, the conventional HCE methods are not effective due to the lack of synchronous voltage and current phasor information in real-field practice. To overcome the phasor limitation, an HCE method based on a generalized admittance criterion (GAC) is proposed in this paper. The proposed GAC aims to determine the dominant harmonic source at the point of common coupling (PCC) from the utility side and customer side. Compared to the conventional method, the developed method only needs the RMS values of the PCC voltage, current, and phase angle difference. Therefore, the synchronous phasor information of voltage and current is no longer required. Meanwhile, a threshold to determine the dominant harmonic source is established by using the equivalent admittance ratio on both sides of PCC. The evaluation process of the proposed method is significantly simplified by comparing the generalized admittance limit with the proposed threshold, which also greatly improves the method evaluation accuracy. Moreover, the interference of background harmonic fluctuation is excluded by using the linear calibration-based harmonic admittance estimation method. Finally, multiple scenarios with various admittance characteristics were simulated to verify the performance of the proposed criterion, and the real-field measurement is also used to demonstrate the accuracy and validity of the proposed method. © 2023
引用
收藏
相关论文
共 5 条
  • [1] A generalized admittance criterion for dominant harmonic source determination without synchronous phasor measurements
    Xu, Qingshen
    Sun, Yuanyuan
    Li, Yahui
    Ding, Lei
    Sun, Kaiqi
    Yin, Shulin
    Yang, Ming
    Liu, Yang
    Cheng, Xingong
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 155
  • [2] Using Harmonic Measurements to Aid in Source Determination during Elevated Voltage Investigations
    Dorr, Doug
    Martino, Salvatore
    Hanebuth, Stuart C.
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [3] The Maximally-Coherent Reference technique and its application to sound source extraction without synchronous measurements
    Albezzawy, Muhammad N.
    Antoni, Jerome
    Leclere, Quentin
    JOURNAL OF SOUND AND VIBRATION, 2025, 599
  • [4] Determination of d and q reactances of permanent-magnet synchronous motors without measurements of the rotor position
    Nee, HP
    Lefevre, L
    Thelin, P
    Soulard, J
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2000, 36 (05) : 1330 - 1335
  • [5] Graph Convolutional Network-Based Multi-harmonic Source Localization Method Without the Need for Synchronous Measurement Data
    Zhu, Yuanzhe
    Wang, Ling
    Du, Wanlin
    Lv, Hong
    Wang, Jinfeng
    2024 THE 7TH INTERNATIONAL CONFERENCE ON ENERGY, ELECTRICAL AND POWER ENGINEERING, CEEPE 2024, 2024, : 784 - 790